VFD fault codes explained across ABB, Allen-Bradley, Danfoss, Siemens, Yaskawa, and Schneider drives with common alarms and practical fix steps.
VFD fault codes explained across ABB, Allen-Bradley, Danfoss, Siemens, Yaskawa, and Schneider drives with common alarms and practical fix steps.
Likely parts to price
Common heat-related VFD and servo-drive failure point.
Useful when the drive display or controls fail.
Price this on braking, deceleration, and overvoltage faults.
Most VFD faults fall into a few repeat patterns: too much current, too much voltage, too little voltage, too much heat, or a bad signal from the motor or control system. Once you know the category, you can narrow the cause fast.
| Fault Family | Common Abbreviations | Typical Cause |
|---|---|---|
| Overcurrent | OC, F001, Fault 7 | Mechanical jam, shorted motor, accel too fast |
| Overvoltage | OV, F003, 3210 | Decel too fast, regenerative load |
| Undervoltage | UV, F004, 3300 | Weak supply, blown fuse, phase loss |
| Overtemperature | OH, oH, 4110 | Dirty fan, blocked airflow, high ambient |
| Ground Fault | GF | Motor winding or cable insulation failure |
| Communication Fault | COM, 9300, F81 | PLC or network problem |
| Overload | OL, F012, 5010 | Motor load above rating |
The drive tried to push more current than its output stage allows. Start with the mechanical load. A stuck conveyor, seized pump, or locked compressor will trip overcurrent even when the drive is healthy.
This shows up during deceleration on high-inertia loads. The motor becomes a generator and pushes energy back into the DC bus. Lengthen the decel ramp or add a brake resistor if the application stops hard.
Check the input fuses and the line voltage under load. A loose terminal or weak transformer can look fine with no load and collapse when the motor starts.
A dirty drive cabinet causes more VFD faults than most people expect. Clean the fan screens, verify the internal fan runs, and make sure the drive has the clearances listed in the manual.
| Brand | Example Guide |
|---|---|
| ABB | ABB VFD Fault Codes |
| Allen-Bradley | Allen-Bradley PowerFlex Fault Codes |
| Danfoss | Danfoss VFD Fault Codes |
| Siemens | Siemens VFD Fault Codes |
| Yaskawa | Yaskawa VFD Fault Codes |
| Eaton | Eaton VFD Fault Codes |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If the drive trips on ground fault, blows input fuses, or shows IGBT or power section errors, stop and test the motor and cable before you restart. A drive shop or field service tech can save you from burning up the replacement drive too.