ABB ACS355 drive Fault 2330 means a ground fault has been detected on the output. Learn causes, diagnostic steps, and how to clear this VFD fault.
ABB ACS355 drive Fault 2330 means a ground fault has been detected on the output. Learn causes, diagnostic steps, and how to clear this VFD fault.
Likely parts to price
First part to price when insulation damage or output-cable leakage is found.
Useful on long motor leads after true insulation faults are ruled out.
Relevant when moisture, tracking, or damaged terminals cause leakage faults.
Fault 2330 on the ABB ACS355 variable frequency drive means the drive has detected a ground fault condition on the output — significant current is flowing from one or more output phases to earth ground. The drive shuts down immediately to prevent damage to the motor and drive output stage.
In a properly wired motor and drive system, output current should flow only through the motor windings — not to ground. A ground fault means current is finding a path to earth through:
| Cause | Likelihood |
|---|---|
| Failed motor winding insulation (aged motor) | High |
| Damaged output cable (chafed or pinched) | High |
| Moisture in motor terminal box | High |
| Long motor cable with high capacitive ground current | Medium |
| Drive output IGBT failure (internal fault) | Medium |
| Incorrect fault 2330 trip (ground fault threshold too sensitive) | Low |
Step 1 — Disconnect the motor cable from the drive
Step 2 — Megger test the motor
Step 3 — Megger test the motor cable
Step 4 — Check for moisture
Step 5 — Check cable length and shielding
Step 6 — Check drive output IGBTs
After identifying and fixing the fault:
| Part | Notes |
|---|---|
| Motor (rewound or replacement) | Match HP, voltage, frame, and poles |
| Motor cable (shielded) | Use shielded 4-conductor cable for VFD applications |
| ACS355 drive | If output IGBT confirmed failed |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: The ABB ACS355 supports a ground fault trip sensitivity parameter. For long cable runs, check parameter 1601 and consult ABB application note AN-14-0046 for capacitive ground current calculations.