ABB ACS310 Fault 3130 - Input Phase Loss Fault

⚡ Quick Answer

ABB ACS310 fault 3130 means input phase loss. Check L1/L2/L3 voltage, input fuses, breaker poles, contactor contacts, and loose terminals.

⚡ AT A GLANCEScroll down for full repair guide
What it meansABB ACS310 fault 3130 means input phase loss. Check L1/L2/L3 voltage, input fuses, breaker poles, contactor contacts, and loose terminals.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededInput fuses
Repair intent

Need this fixed instead of diagnosed?

ABB ACS310 fault 3130 means input phase loss. Check L1/L2/L3 voltage, input fuses, breaker poles, contactor contacts, and loose terminals.

Likely parts to price

Price the common parts before you book service.

Input fuses

Low-cost line-side part to check when one phase is missing or unstable.

Input contactor

Price this when a pole is burned, intermittent, or not closing under load.

Line reactor

Useful for sag, imbalance, and harsh incoming power conditions.

ABB ACS310 Fault 3130 — What It Means

Fault 3130 on the ABB ACS310 variable frequency drive indicates an input phase loss — one or more of the three input supply phases is missing or has dropped below the threshold the drive requires for stable operation. The ACS310 monitors input voltage symmetry; if any phase is absent or severely unbalanced, it faults to protect the internal rectifier and DC bus capacitors from unbalanced voltage stress.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Measure input voltage at the drive terminals — With a multimeter, measure L1-L2, L2-L3, and L1-L3 at the drive’s input terminals under load. All three readings should be equal (within 2%). A missing or low reading identifies the faulted phase.
  2. Check input fuses — Open the upstream disconnect and test all three input fuses with a multimeter. A blown fuse reads open. Replace if bad — always replace all three when one blows.
  3. Inspect input terminal connections — Check the torque on all L1/L2/L3 lug screws at the drive. Loose connections cause intermittent phase loss that gets worse under heat.
  4. Inspect the upstream contactor (if installed) — Check contactor contacts for pitting or burning on the affected phase. A failed contact often shows burn marks or unequal wear vs. the other phases.
  5. Reset the fault — After correcting the input issue, restore power and reset the ACS310 (press STOP/RESET on the keypad). Confirm 3130 does not return on restart.

Parts Often Needed

PartNotes
Input fuses (Class J or equivalent)Match to ACS310 input current rating — replace all three
Input contactorReplace if contacts are burned or pitted
Input terminal blockIf lug damage is found during inspection

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Phase loss diagnosis requires working in live panels with dangerous voltages. If you’re not qualified to work on industrial electrical enclosures with exposed live terminals, have a licensed electrician trace and repair the input circuit.


Need a professional? Compare Industrial repair options before replacing parts.