Cooling fan
Common VFD, drive, UPS, and cabinet overheating failure point.
Schneider Altivar ATV71 fault code guide covering OCF, ObF, OHF, PHF, USF, SOF, SCF, LFF, and output phase faults.
Schneider Altivar ATV71 fault code guide covering OCF, ObF, OHF, PHF, USF, SOF, SCF, LFF, and output phase faults.
Likely parts to price
Common VFD, drive, UPS, and cabinet overheating failure point.
Useful to price when faults involve display, keypad, or operator-panel behavior.
Low-cost first check for power-stage and line-side faults.
Price this on drive overvoltage, braking, or deceleration faults.
The Schneider Electric Altivar 71 is a variable frequency drive used on pumps, fans, conveyors, compressors, and process machinery. ATV71 faults usually point to one of five areas: incoming power, motor wiring, load condition, braking/deceleration setup, or cabinet cooling.
| Code | Meaning | First Check |
|---|---|---|
| OCF | Overcurrent | Motor leads, shorted cable, jammed load |
| ObF | Overbraking or DC bus overvoltage | Decel ramp, braking resistor, regen load |
| OHF | Drive overheating | Fan, heatsink, cabinet temperature |
| OLF | Motor overload | Motor current, load, motor nameplate setup |
| PHF | Input phase loss | Supply fuses, contactor, L1/L2/L3 balance |
| OPF1 / OPF2 | Output phase loss | Motor terminals and cable continuity |
| SCF1 / SCF3 / SCF4 | Motor short circuit or ground fault | Megger motor and cable separately |
| SOF | Overspeed | Encoder feedback, speed loop, load overhauling |
| USF | Undervoltage | Incoming line voltage under load |
| LFF | Loss of 4-20 mA signal | Analog input loop and transmitter power |
| Part | Notes |
|---|---|
| Cooling fan kit | Common on older ATV71 cabinets with OHF |
| Braking resistor | Needed when ObF appears during aggressive deceleration |
| Input fuses | Replace only with the specified class and rating |
| Motor cable | Replace if insulation fails megger testing |
| Replacement ATV71 or retrofit drive | Consider when SCF or OCF persists with motor leads disconnected |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Call a qualified drive technician if OCF, SCF, or OHF returns with the motor disconnected. That points to an internal power module, current sensor, or cooling fault inside the drive.