Cooling fan
Common VFD, drive, UPS, and cabinet overheating failure point.
Danfoss VLT Micro FC 51 alarms 13, 14, 29, 38, and 46. Check motor cables, earth faults, cooling, phase loss, and internal faults.
Danfoss VLT Micro FC 51 alarms 13, 14, 29, 38, and 46. Check motor cables, earth faults, cooling, phase loss, and internal faults.
Likely parts to price
Common VFD, drive, UPS, and cabinet overheating failure point.
Useful to price when faults involve display, keypad, or operator-panel behavior.
Low-cost first check for power-stage and line-side faults.
Price this on drive overvoltage, braking, or deceleration faults.
The Danfoss VLT Micro Drive FC 51 is a compact VFD used on small fans, pumps, conveyors, and OEM equipment. Danfoss lists the FC 51 as a limited lifecycle product, so troubleshooting often comes down to deciding whether the fault is an external wiring/load problem or a replacement-drive event.
| Code | Meaning | First Check |
|---|---|---|
| Alarm 13 | Overcurrent | Motor cable, acceleration ramp, jammed load |
| Alarm 14 | Earth fault | Motor insulation and cable damage |
| Alarm 16 | Short circuit | Output terminals and motor leads |
| Alarm 27 | Brake chopper fault | Braking resistor and wiring |
| Alarm 29 | Heatsink temperature | Cooling path and ambient temperature |
| Alarm 30 / 31 / 32 | Motor phase U/V/W missing | Motor cable continuity |
| Alarm 38 | Internal fault | Power cycle once, then replace or repair if it returns |
| Alarm 46 | Power card supply | Internal supply or power card issue |
| Alarm 47 | 24 V supply low | Control wiring load or internal supply |
| Alarm 51 | AMA check failed | Motor data and motor connection |
| Part | Notes |
|---|---|
| Replacement FC 51 drive | Common when Alarm 38 or Alarm 46 returns |
| Motor cable | Replace after failed insulation test |
| Braking resistor | Check when stop-time faults appear |
| Cabinet fan and filters | Cheap fix for repeated temperature trips |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Call a qualified technician for any Alarm 14, Alarm 16, or Alarm 38 that repeats after the motor cable is disconnected. Those faults can involve dangerous stored DC voltage and failed power electronics.