Yaskawa VFD Fault OC — Overcurrent Fix

Verified by Certified Technician
Jump to Fix View Parts

Error Code: Yaskawa VFD Fault OC

What it means: The OC fault on Yaskawa J1000, V1000, and A1000 series variable frequency drives indicates that the output current exceeded 200% of the drive’s rated output current. The drive’s hardware overcurrent comparator (independent of software current limiting) detected this condition and shut down the output IGBTs in under 10 microseconds to prevent drive damage. This is a hardware-level trip, not a software protection — it means the current spike was severe and instantaneous.

OC is distinct from Yaskawa’s OL1 (motor overload) and OL2 (drive overload) faults, which are software-based thermal models that trip on sustained overcurrent. OC is a fast, hard trip from a momentary spike.

Common Causes

Step-by-Step Fix {#step-by-step-fix}

  1. Do not clear and restart immediately. An OC fault from a short circuit will destroy the drive’s output stage if you reset and restart without investigation. The drive has already done its job by shutting down in microseconds — give it the same respect and investigate before re-energizing.

  2. Disconnect the motor leads from the drive output terminals (T1/U, T2/V, T3/W). With LOTO applied, physically disconnect all three output phase leads from the drive. This isolates the drive from the motor and cable.

  3. Test the motor for winding and insulation faults. Using a 500V megohmmeter, measure from each phase lead to motor frame ground. Minimum acceptable reading is 1 MΩ; healthy motors read 100 MΩ+. Also measure phase-to-phase resistance at the motor terminals — balance within 5% is expected. Any short, ground, or unbalanced winding reading means the motor is failed.

  4. Test the motor cable for ground faults. With the motor disconnected from the cable at the motor terminal box, measure resistance from each conductor to the cable shield or conduit. Any reading below 1 MΩ indicates a damaged cable that needs replacement.

  5. With motor and cable disconnected, attempt a drive-only test. Reconnect power to the drive (without motor leads connected). Attempt to run the drive to 60 Hz on the digital operator (LOCAL mode). If OC occurs with no motor connected, a drive output IGBT has failed — the drive requires repair or replacement.

  6. Increase the acceleration time (C1-01 on A1000, b1-17 on V1000, C1-01 on J1000). If motor and cable tested good, the fault was caused by excessive acceleration rate. On Yaskawa drives, C1-01 is Acceleration Time 1. Increase by 50–100% and test with the motor reconnected. For V/f mode applications, also consider enabling the stall prevention function (L3-01 through L3-04 on A1000).

  7. Verify motor insulation for a drive application. Yaskawa drives produce high dV/dt output waveforms (voltage rise times of 500–2000 V/µs). Standard NEMA B motors with older insulation systems can fail at the first winding turn due to this stress. If the motor is older than 10 years and the OC fault appears at a specific point in every acceleration, consider replacing the motor with an inverter-duty rated unit or adding a Yaskawa dV/dt filter (part LCRD series) at the drive output.

  8. Check and clear the fault history. Yaskawa drives store the last 4 faults in U2 monitors (U2-01 through U2-04 on A1000). U2-02 shows the output current at the time of the fault, U2-03 shows output frequency. This data helps confirm whether the OC was at startup (0 Hz, indicating a wiring short) or mid-acceleration (indicating a ramp time issue).

Parts That May Need Replacement {#parts-that-may-need-replacement}

PartPart NumberTypical CostWhere to Buy
Yaskawa dV/dt Output FilterLCRD series (size by drive A)$150–$600Yaskawa distributor
Inverter-duty MotorNEMA MG1 Part 31 rated$300–$2000+Grainger / motor shop
Replacement J1000 DriveCIMR-JU2A0004FAA (varies)$300–$700Yaskawa distributor / Amazon
Motor Cable (THHN shielded)By footage$2–$8/ftGrainger / electrical supply

When to Call a Professional

If drive-only testing (Step 5) produces an OC fault with no motor connected, the drive has a failed output IGBT module. IGBT replacement in Yaskawa drives is possible but requires component-level repair experience, IGBT handling precautions, and a gate driver test before reassembly. For smaller drives (J1000 under 3 HP), replacement is often more economical than repair. For larger A1000 drives, an authorized Yaskawa repair center can often replace IGBT modules and retest for significantly less than a new drive. Do not attempt to operate a drive with a suspected failed IGBT — you risk damaging the input rectifier and control board in addition to the output stage.

Pro tip: Yaskawa OC faults that occur at a repeatable output frequency (e.g., always at 15 Hz) during acceleration often point to a mechanical resonance frequency — the load’s natural vibration frequency aligns with the drive output, causing current oscillation that trips OC. Yaskawa drives include a Jump Frequency function (d3-01 through d3-04) that skips specific output frequencies. Enabling jump frequency around the resonant point eliminates these faults without changing any mechanical components.