Yaskawa A1000 OC Fault — Overcurrent

3 min read
⚡ Quick Answer

Yaskawa A1000 drive OC fault means overcurrent on the output. Learn causes, how to diagnose OCA, OCb, OCC variants, parameter fixes, and hardware checks.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa A1000 OC Fault — Overcurrent

The OC fault on the Yaskawa A1000 high-performance vector drive means output current has exceeded approximately 200% of rated drive current (instantaneous trip). The drive shuts down immediately. The A1000 is Yaskawa’s medium-heavy-duty drive used in demanding applications including conveyors, compressors, fans, and pumps.

A1000 OC Fault Variants

CodePhaseDescription
OCAAccelerationOvercurrent during speed ramp-up
OCbDecelerationOvercurrent during speed ramp-down
OCCConstant speedOvercurrent at steady state
OCAt stopOvercurrent at zero speed (short circuit suspect)

Jump to Fix

Common Causes

CauseFault VariantLikelihood
Acceleration ramp too aggressiveOCAVery High
Mechanical load jam or seized bearingOCCHigh
Deceleration ramp too fast (high inertia load)OCbHigh
Incorrect V/f or vector control tuningOCAMedium
Short circuit in motor cable or motorOCA / OCMedium
Failed output IGBTOCAMedium
Load demand spike (starting against back-pressure)OCAMedium

Step-by-Step Diagnosis

Step 1 — Identify the fault type Check the A1000 fault log (U2-01 through U2-10 store recent faults with conditions):

Step 2 — Extend ramp times (OCA / OCb)

Step 3 — Check mechanical system

Step 4 — Run motor auto-tune

Step 5 — Megger test motor and cable

Step 6 — Check IGBT output stage

Key A1000 Parameters for OC Faults

ParameterFunctionOC-Relevant Setting
C1-01Acceleration Time 1Increase for OCA
C1-02Deceleration Time 1Increase for OCb
L3-01Stall Prevention — acceleration1 (enabled) for variable loads
L3-04Stall Prevention — constant speed1 (enabled)
L3-06Stall Prevention — decelerationAdjust for high-inertia loads
E1-01Input voltage settingMust match actual supply
T1-01Auto-tune selectionRun after new motor or OC fault

A1000 vs V1000 OC Comparison

FeatureV1000A1000
Frame size0.5–20 HP1–600+ HP
Torque controlV/f + Basic closed loopFull closed-loop vector
OC trip level200% rated200% rated
Braking resistorOptionalStandard on most frames

Pro tip: The A1000 supports S-curve acceleration (C2-01 through C2-04) which smooths the ramp profile. Enabling S-curve significantly reduces OCA faults on applications with high starting torque requirements like conveyors or compressors.