Yaskawa A1000 drive OC fault means overcurrent on the output. Learn causes, how to diagnose OCA, OCb, OCC variants, parameter fixes, and hardware checks.
Yaskawa A1000 drive OC fault means overcurrent on the output. Learn causes, how to diagnose OCA, OCb, OCC variants, parameter fixes, and hardware checks.
Likely parts to price
Price this when overcurrent or overload faults trace to damaged output wiring.
Relevant when the driven load binds, stalls, or pulls excessive current.
Useful to compare after nameplate current and drive parameters are verified.
The OC fault on the Yaskawa A1000 high-performance vector drive means output current has exceeded approximately 200% of rated drive current (instantaneous trip). The drive shuts down immediately. The A1000 is Yaskawa’s medium-heavy-duty drive used in demanding applications including conveyors, compressors, fans, and pumps.
| Code | Phase | Description |
|---|---|---|
| OCA | Acceleration | Overcurrent during speed ramp-up |
| OCb | Deceleration | Overcurrent during speed ramp-down |
| OCC | Constant speed | Overcurrent at steady state |
| OC | At stop | Overcurrent at zero speed (short circuit suspect) |
| Cause | Fault Variant | Likelihood |
|---|---|---|
| Acceleration ramp too aggressive | OCA | Very High |
| Mechanical load jam or seized bearing | OCC | High |
| Deceleration ramp too fast (high inertia load) | OCb | High |
| Incorrect V/f or vector control tuning | OCA | Medium |
| Short circuit in motor cable or motor | OCA / OC | Medium |
| Failed output IGBT | OCA | Medium |
| Load demand spike (starting against back-pressure) | OCA | Medium |
Step 1 — Identify the fault type Check the A1000 fault log (U2-01 through U2-10 store recent faults with conditions):
Step 2 — Extend ramp times (OCA / OCb)
Step 3 — Check mechanical system
Step 4 — Run motor auto-tune
Step 5 — Megger test motor and cable
Step 6 — Check IGBT output stage
| Parameter | Function | OC-Relevant Setting |
|---|---|---|
| C1-01 | Acceleration Time 1 | Increase for OCA |
| C1-02 | Deceleration Time 1 | Increase for OCb |
| L3-01 | Stall Prevention — acceleration | 1 (enabled) for variable loads |
| L3-04 | Stall Prevention — constant speed | 1 (enabled) |
| L3-06 | Stall Prevention — deceleration | Adjust for high-inertia loads |
| E1-01 | Input voltage setting | Must match actual supply |
| T1-01 | Auto-tune selection | Run after new motor or OC fault |
| Feature | V1000 | A1000 |
|---|---|---|
| Frame size | 0.5–20 HP | 1–600+ HP |
| Torque control | V/f + Basic closed loop | Full closed-loop vector |
| OC trip level | 200% rated | 200% rated |
| Braking resistor | Optional | Standard on most frames |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: The A1000 supports S-curve acceleration (C2-01 through C2-04) which smooths the ramp profile. Enabling S-curve significantly reduces OCA faults on applications with high starting torque requirements like conveyors or compressors.