Input fuses
Low-cost line-side part to check when one phase is missing or unstable.
What Yaskawa A1000 UV1 means, why the drive sees DC bus undervoltage, and how to diagnose input power, contactor, and weak-supply problems.
What Yaskawa A1000 UV1 means, why the drive sees DC bus undervoltage, and how to diagnose input power, contactor, and weak-supply problems.
Likely parts to price
Low-cost line-side part to check when one phase is missing or unstable.
Price this when a pole is burned, intermittent, or not closing under load.
Useful for sag, imbalance, and harsh incoming power conditions.
Yaskawa A1000 Fault UV1 means the drive detected DC bus undervoltage. In practice, the inverter’s main circuit voltage has dropped below the minimum level needed for stable operation. On the plant floor, UV1 usually points to missing input phase, brownout conditions, loose power wiring, a dropping line contactor, or a supply that sags hard when the motor tries to accelerate.
UV1 is often intermittent at first. Operators will report that the line ran fine yesterday, but now the drive trips on startup, during acceleration, or whenever another large load comes online.
| Part | Notes |
|---|---|
| Class J or semiconductor input fuses | Replace blown or heat-damaged line protection after finding the cause |
| Three-pole contactor | Weak or pitted contacts can create intermittent voltage drop |
| 3% line reactor | Helps stabilize weak or noisy incoming power |
| Power quality meter | Best way to prove supply sag during startup |
| Terminal block and ferrule kit | Useful when loose or overheated line-side terminations caused the fault |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Call a drive technician or electrician if UV1 persists with verified balanced input voltage at the drive terminals. At that point you may be dealing with failing DC bus capacitors, a bad precharge circuit, or a deeper power-distribution problem upstream of the drive.