Drive cooling fan
Common heat-related VFD and servo-drive failure point.
Troubleshoot Yaskawa UV1 on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Troubleshoot Yaskawa UV1 on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Likely parts to price
Common heat-related VFD and servo-drive failure point.
Useful when the drive display or controls fail.
Price this on braking, deceleration, and overvoltage faults.
Yaskawa fault UV1 means main circuit undervoltage — the DC bus voltage dropped below the low-voltage detection level during operation. On Yaskawa V1000, A1000, and GA700 drives, UV1 is a protective shutdown that occurs when input voltage is lost or drops significantly during operation. Unlike UV2 (control power undervoltage) or UV3 (soft-charge circuit fault), UV1 specifically indicates the main power circuit lost its voltage source. The drive can’t maintain motor control with insufficient DC bus voltage, so it trips cleanly rather than allow uncontrolled deceleration.
| Part | Notes |
|---|---|
| Input fuses (semiconductor type) | Yaskawa specifies fuse type and current rating in the drive manual |
| DC bus capacitors | Replacement is practical on larger drives; requires capacitor reformation procedure |
| Line reactor | Reduces the impact of utility voltage sags on the DC bus |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Aged capacitor diagnosis requires a capacitance meter and knowledge of proper capacitor reformation procedures. For drives over 5 years old with frequent UV1, a Yaskawa service tech can evaluate bus capacitor health.