Drive cooling fan
Common heat-related VFD and servo-drive failure point.
Troubleshoot Yaskawa VFD fault SC on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Troubleshoot Yaskawa VFD fault SC on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Likely parts to price
Common heat-related VFD and servo-drive failure point.
Useful when the drive display or controls fail.
Price this on braking, deceleration, and overvoltage faults.
Yaskawa VFD fault SC (IGBT Short Circuit or Gate Drive Fault) indicates that the drive detected a short circuit condition on its output IGBT (insulated gate bipolar transistor) stage. The gate drive circuit monitors current through each IGBT switch, and when current spikes to a level indicating a short — either between two output phases, from an output phase to the DC bus, or through a failed IGBT itself — the gate drive fires a hardware overcurrent protection and shuts down the drive in microseconds. SC is a hard fault that cannot be cleared by software reset if the hardware fault condition still exists.
| Part | Notes |
|---|---|
| Drive IGBT module / power board | Must match drive voltage/current rating; Yaskawa components are model-specific |
| Motor (replace or rewind) | If winding short is confirmed; rewinding larger motors is cost-effective |
| Output cable | Replace if insulation damage or conductor-to-conductor short found |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
SC faults involving failed IGBTs inside the drive require capacitor discharge verification, high-voltage PPE, and component-level knowledge. IGBT module replacement on industrial drives is typically performed by a Yaskawa service technician or certified drive repair center.