Danfoss VLT 2900 Fault Codes: Complete Guide

⚡ Quick Answer

Danfoss VLT 2900 VFD fault codes and diagnostics. AL-series alarm codes, causes, and technician-level troubleshooting for VLT 2900 drives.

⚡ AT A GLANCEScroll down for full repair guide
What it meansDanfoss VLT 2900 VFD fault codes and diagnostics. AL-series alarm codes, causes, and technician-level troubleshooting for VLT 2900 drives.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededCooling fan
Repair intent

Need this fixed instead of diagnosed?

Danfoss VLT 2900 VFD fault codes and diagnostics. AL-series alarm codes, causes, and technician-level troubleshooting for VLT 2900 drives.

Likely parts to price

Price the common parts before you book service.

Cooling fan

Common VFD, drive, UPS, and cabinet overheating failure point.

Control keypad

Useful to price when faults involve display, keypad, or operator-panel behavior.

Fuses

Low-cost first check for power-stage and line-side faults.

Braking resistor

Price this on drive overvoltage, braking, or deceleration faults.

Danfoss VLT 2900 Fault Codes

The Danfoss VLT 2900 series is a general-purpose VFD rated 0.37-30 kW. Alarm codes display on the LCP (Local Control Panel) as “AL” followed by a number. Warning codes display as “W” codes. The VLT 2900 is an older series - replacement is the VLT FC301/302 family.

VLT 2900 Fault Code Table

CodeFault DescriptionCommon CauseAction
AL 110V supply low10V reference output shortedCheck terminal 50 wiring
AL 2Live zero faultReference input below minimumCheck analog input signal
AL 4Phase loss (motor)Missing output phaseCheck motor connections
AL 5DC link overvoltageRegeneration or voltage spikeExtend decel ramp, add brake
AL 7DC link overvoltage (fault)Persistent overvoltageCheck input voltage
AL 13OvercurrentMotor short or overloadMegger test motor, reduce load
AL 14Ground faultMotor winding groundMegger test motor
AL 15Drive incompatibleWrong hardwareCheck drive model
AL 16Short circuitOutput short circuitCheck motor and cables
AL 17Control word timeoutSerial communication lossCheck network connection
AL 25Brake resistor shortBrake resistor failureCheck brake resistor resistance
AL 29Heatsink overtempCooling blocked or high ambientClean fins, check fan
AL 34Communication faultFieldbus timeoutCheck communication network
AL 38Motor thermal limitMotor overtemperatureReduce load, check motor cooling
AL 41Analog input 53 lowSignal below minimumCheck signal from sensor/controller

Most Common VLT 2900 Faults

AL 13 - Overcurrent

The VLT 2900 is sensitive to output impedance. Verify motor data in parameters 102-106 (nameplate data). Increase parameter 207 (acceleration time). If the fault is immediate on start, check for a short circuit at output terminals.

AL 29 - Heatsink Overtemperature

VLT 2900 units installed in enclosures must have adequate ventilation. Heatsink temperature limit is 90 degrees C. Clean fins with compressed air. In enclosed panels, provide fan-forced cooling with adequate airflow through the panel.

Most common on applications with high inertia loads (fans, pumps, centrifuges). The VLT 2900 DC bus charges if motor decelerates faster than the drive absorbs energy. Extend decel time (parameter 208) or add brake chopper/resistor.

AL 14 - Ground Fault

Use megohmmeter at 1000 VDC on all motor windings and cables. Also check PE (ground) connection integrity at both motor and drive. Long cables act as capacitors and can cause nuisance ground fault trips on older drives.

Parts Commonly Needed

PartNotes
LCP control panelAvailable as replacement accessory
Brake resistorMatch resistance and power rating
Cooling fanSpecific to VLT 2900 frame size
FusesNote: VLT 2900 uses specific semiconductor fuse types

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Pro tip: Danfoss VLT 2900 drives are discontinued. When parts are no longer available, the FC301/FC302 is the recommended migration path. Danfoss provides a parameter migration guide for converting VLT 2900 parameters to FC302 equivalents.