Allen-Bradley PowerFlex 70 Fault Codes - F2, F5, F7, F13, and F111

⚡ Quick Answer

PowerFlex 70 faults cover auxiliary input, power loss, overvoltage, motor overcurrent, ground fault, phase loss, and internal hardware trips.

⚡ AT A GLANCEScroll down for full repair guide
What it meansPowerFlex 70 faults cover auxiliary input, power loss, overvoltage, motor overcurrent, ground fault, phase loss, and internal hardware trips.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededVFD-rated motor cable
Repair intent

Need this fixed instead of diagnosed?

PowerFlex 70 faults cover auxiliary input, power loss, overvoltage, motor overcurrent, ground fault, phase loss, and internal hardware trips.

Likely parts to price

Price the common parts before you book service.

VFD-rated motor cable

Price this when overcurrent or overload faults trace to damaged output wiring.

Motor bearings or coupling

Relevant when the driven load binds, stalls, or pulls excessive current.

Motor overload protection

Useful to compare after nameplate current and drive parameters are verified.

Allen-Bradley PowerFlex 70 Fault Codes

The Allen-Bradley PowerFlex 70 is a mid-range VFD rated 0.37-448 kW. Fault codes display on the HIM (Human Interface Module) as fault numbers. The PowerFlex 70 uses a similar fault structure to the PF700 and PF755 but with its own parameters (accessible via Connected Components Workbench or DriveExplorer).

PowerFlex 70 Fault Code Table

CodeFault DescriptionCommon CauseAction
F2Auxiliary inputExternal fault from TB6Check external fault wiring
F3Power lossInput power interruptionCheck supply voltage
F4UndervoltageLow supply voltageVerify input voltage
F5OvervoltageRegenerative energy or voltage spikeAdd brake resistor
F6Motor stallMotor stalled or overloadedCheck mechanical load
F7Motor overcurrentMotor overload or winding faultCheck motor amps and winding
F8Heatsink overtemperatureHigh ambient or blocked coolingClean fins, check fan
F12HW overcurrentHardware overcurrent (fast)Check for short circuit
F13Ground faultMotor winding or cable groundMegger test motor
F15Load lossBelt broken or load disconnectCheck mechanical connection
F23Auto tune faultMotor data entry errorVerify motor nameplate data
F25Drive overtemperatureInternal temperature highCheck cooling system
F33Start inhibitSafety input or logic inhibitCheck digital input wiring
F38Phase lossOutput phase missingCheck motor connections
F63Software faultParameter or firmware issueReset and reload parameters
F111Internal faultHardware faultContact Rockwell support

Most Common PowerFlex 70 Faults

F7 - Motor Overcurrent

Check motor nameplate FLA vs. parameter P032 (motor NP amps). Verify correct motor overload setting. Check motor for single-phasing, winding imbalance, or locked rotor condition. Increase accel time (parameter A051).

F8 - Heatsink Overtemperature

The PowerFlex 70 requires 3-inch clearance on all sides. Clean fins with compressed air - debris accumulates on the cooling fins rapidly in industrial environments. Check internal cooling fan (starts automatically with drive power).

F13 - Ground Fault

Disconnect motor leads at drive output terminals. Megger test each conductor to ground at 1000 VDC. Reading below 1 Mohm indicates a failed cable or motor winding. Also check cable tray for damaged insulation.

F5 - Overvoltage

Pumping applications with fast deceleration cause motor regeneration. Increase deceleration ramp time (parameter A052). If regeneration is unavoidable, add a dynamic braking resistor to the brake resistor terminals.

Parts Commonly Needed

PartNotes
HIM modulePlug-in display - model 20-HIM-A3 is most common
Cooling fanMatch PowerFlex 70 frame size
Input fusesClass J or CC - match ampere rating
Brake resistorMatch ohm and watt rating to drive

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Pro tip: PowerFlex 70 stores fault queue (F01-F08 parameters in the fault log group). Access via HIM: DIAGNOSTICS -> FAULT LOG. Always review the full fault queue - a single event often produces multiple faults in sequence that tell the root cause story.

Quick FAQ

What does PowerFlex 70 fault F7 mean?

F7 is motor overcurrent. Check motor nameplate FLA against parameter P032 (motor NP amps), verify the motor overload setting, and check for single-phasing, winding imbalance, or a locked rotor condition. Increasing accel time (parameter A051) can also help.

How much clearance does a PowerFlex 70 need to avoid F8 overtemperature?

The PowerFlex 70 requires 3-inch clearance on all sides. Clean the cooling fins with compressed air, since debris accumulates rapidly in industrial environments, and check that the internal cooling fan starts automatically with drive power.

How do I test for a PowerFlex 70 F13 ground fault?

Disconnect the motor leads at the drive output terminals, then megger test each conductor to ground at 1000 VDC. A reading below 1 Mohm indicates a failed cable or motor winding. Also check the cable tray for damaged insulation.

Where do I view the PowerFlex 70 fault queue?

Access it via the HIM: DIAGNOSTICS -> FAULT LOG, which stores F01-F08 in the fault log parameter group. Always review the full fault queue, since a single event often produces multiple faults in sequence that tell the root cause story.