ABB VFD Fault 2310 - Earth Fault and Insulation Checks

⚡ Quick Answer

ABB VFD fault 2310 means earth fault. Check motor winding insulation, output cable damage, wet terminal boxes, long cable runs, and output reactors.

⚡ AT A GLANCEScroll down for full repair guide
What it meansABB VFD fault 2310 means earth fault. Check motor winding insulation, output cable damage, wet terminal boxes, long cable runs, and output reactors.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededVFD-rated motor cable
Repair intent

Need this fixed instead of diagnosed?

ABB VFD fault 2310 means earth fault. Check motor winding insulation, output cable damage, wet terminal boxes, long cable runs, and output reactors.

Likely parts to price

Price the common parts before you book service.

VFD-rated motor cable

First part to price when insulation damage or output-cable leakage is found.

Output line reactor

Useful on long motor leads after true insulation faults are ruled out.

Motor terminal kit

Relevant when moisture, tracking, or damaged terminals cause leakage faults.

ABB VFD Fault 2310 — What It Means

ABB VFD fault 2310 is an earth fault (ground fault). The drive’s earth fault detection circuit detected that current is flowing from one or more output phases to earth (ground) at a level above the detection threshold. This indicates that the insulation on the motor winding, output cable, or motor terminal box has broken down and is conducting current to ground. ABB drives detect this condition by monitoring the sum of all three output phase currents — in a healthy system with no ground fault, the vector sum is zero. A non-zero residual current indicates a fault to ground.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Disconnect the motor from the drive output — Remove the motor cable connections at the drive’s T1/T2/T3 (U/V/W) output terminals. Attempt to run the drive unloaded (if the drive supports test mode). If fault 2310 clears, the fault is in the motor or cable. If it persists, investigate the drive output section.
  2. Megger test the motor — With the motor cable disconnected at both the drive and motor ends, perform an insulation resistance test (megger) between each phase terminal and motor frame ground. Values below 1 MΩ indicate degraded insulation. Values below 100 kΩ indicate a serious fault.
  3. Megger test the output cable — Test each conductor of the output cable against the ground/shield. Any low-resistance reading indicates damaged cable insulation.
  4. Inspect motor terminal box — Open the motor terminal box and check for moisture, corrosion, tracking marks (carbon paths), or physical damage between phase lugs and the motor body.
  5. Add output reactor for long cable runs — If no insulation failure is found, install an output line reactor (choke) between the drive and the motor to reduce the capacitive ground current to below the detection threshold.

Parts Often Needed

PartNotes
Motor (rewind or replace)If megger confirms winding fault; rewinding is cost-effective on larger motors
Output cableReplace full run if insulation is compromised
Output line reactor (choke)Install when cable run exceeds drive manufacturer’s maximum without reactor

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Megger testing at 500V or 1000V DC on motors connected to high-voltage systems requires proper PPE and lock-out/tag-out procedures. If the motor is part of a hazardous location installation, a licensed electrician must perform the insulation testing and repair.