ACS580 input fuses
Match the type and amperage from the ACS580 hardware manual for the specific frame size.
ABB ACS580 fault 3130 input-phase-loss guide for blown fuses, loose L1/L2/L3 terminals, contactors, supply imbalance, and parameter 31.22.
Parts to price first
Match the type and amperage from the ACS580 hardware manual for the specific frame size.
Replace if contact inspection shows pitting or high resistance under load.
Replace if the existing L1/L2/L3 lug is corroded or cracked; re-torque to the hardware manual spec.
For measuring L1-L2, L2-L3, and L1-L3 balance at the drive input.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
ABB ACS580 fault 3130 input-phase-loss guide for blown fuses, loose L1/L2/L3 terminals, contactors, supply imbalance, and parameter 31.22.
The ABB ACS580 is a general-purpose all-compatible drive designed for industrial pump, fan, and compressor applications. It is the successor to the ACS550 in the ABB product line. Fault 3130 (INPUT PHASE LOSS) indicates the drive has detected a missing or severely unbalanced phase on its three-phase input supply. Like other ABB drives, the ACS580 detects phase loss by monitoring DC bus ripple — a lost input phase creates a characteristic 2× ripple frequency on the DC bus. When ripple exceeds the threshold, the drive trips on 3130 to protect the rectifier and DC bus capacitors from unbalanced stress.
| Part | Notes |
|---|---|
| Input fuses | Match the type and amperage from the ACS580 hardware manual for the specific frame size |
| AC contactor | Replace if contact inspection shows pitting or high resistance under load |
| Power terminal lug | Replace if existing lug is corroded or cracked |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If all three supply voltages are confirmed balanced and correct at the drive input terminals but fault 3130 persists, the rectifier input section may have been damaged by a prior phase loss event. ABB has an authorized drive repair center network for board-level diagnosis and repair. The ACS580 hardware warranty covers manufacturing defects; a phase-loss-induced rectifier failure may or may not be covered depending on the cause.
Fault 3130 (INPUT PHASE LOSS) means the drive detected a missing or severely unbalanced phase on its three-phase input supply. The ACS580 watches DC bus ripple; a lost phase produces a characteristic 2x ripple frequency, and when ripple exceeds the threshold the drive trips to protect the rectifier and DC bus capacitors.
A blown upstream input fuse on one phase is the most common cause. It creates a single-phase condition at the drive input. Loose L1, L2, or L3 compression lugs and burned upstream contactor contacts are the next most likely causes.
Measure phase-to-phase voltage at the drive input terminal block with the drive powered. If L1-L2 and L2-L3 read normal but L1-L3 reads zero or very low, L2 is the problem phase. Then test the upstream fuse on that phase and inspect its terminal lug and contactor contact.
Only if supply voltage quality is marginal and 3130 is a nuisance trip. Setting parameter 31.22 (SUPPLY PHASE LOSS) to WARNING lets the drive log A3130 and ride through brief imbalance. Do not do this if the underlying phase loss is a persistent fault.
If all three supply voltages are confirmed balanced and correct at the drive input terminals but 3130 persists, the rectifier input section may have been damaged by a prior phase loss event. That needs board-level diagnosis at an ABB authorized drive repair center.