ABB ACS580 Fault 3130 - Input Phase Loss Fix

⚡ Quick Answer

ABB ACS580 fault 3130 input-phase-loss guide for blown fuses, loose L1/L2/L3 terminals, contactors, supply imbalance, and parameter 31.22.

⚡ AT A GLANCEScroll down for full repair guide
What it meansFault 3130 (INPUT PHASE LOSS) means the ACS580 detected a missing or severely unbalanced phase on its three-phase input, seen as excess DC bus ripple.
Most likely causeBlown upstream input fuse, loose L1/L2/L3 compression lug, burned upstream contactor contact, utility voltage imbalance over 3%, or parameter 31.22 set to FAULT on a marginal supply.
First checkMeasure L1-L2, L2-L3, and L1-L3 at the drive input; all three should be within 3% of each other and within ±10% of nominal.
⏱Repair time30-90 minutes for fuse, lug, or contactor work after a 5-minute capacitor discharge wait
🔧Part neededInput fuses, AC contactor, power terminal lug

Parts to price first

Check the part before you book service.

ACS580 input fuses

Match the type and amperage from the ACS580 hardware manual for the specific frame size.

Three-phase AC contactor

Replace if contact inspection shows pitting or high resistance under load.

Power terminal compression lug

Replace if the existing L1/L2/L3 lug is corroded or cracked; re-torque to the hardware manual spec.

True-RMS multimeter

For measuring L1-L2, L2-L3, and L1-L3 balance at the drive input.

Equipment service manual download (eManualOnline)

The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.

Repair intent

Need this fixed instead of diagnosed?

ABB ACS580 fault 3130 input-phase-loss guide for blown fuses, loose L1/L2/L3 terminals, contactors, supply imbalance, and parameter 31.22.

ABB ACS580 Fault 3130 — What It Means

The ABB ACS580 is a general-purpose all-compatible drive designed for industrial pump, fan, and compressor applications. It is the successor to the ACS550 in the ABB product line. Fault 3130 (INPUT PHASE LOSS) indicates the drive has detected a missing or severely unbalanced phase on its three-phase input supply. Like other ABB drives, the ACS580 detects phase loss by monitoring DC bus ripple — a lost input phase creates a characteristic 2× ripple frequency on the DC bus. When ripple exceeds the threshold, the drive trips on 3130 to protect the rectifier and DC bus capacitors from unbalanced stress.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Check all three input voltages at L1, L2, L3 — Measure each phase-to-phase voltage at the drive input terminal block with the drive powered. All three readings should be within 3% of each other and within ±10% of nominal.
  2. Identify the missing phase — A zero or significantly reduced reading on one pair of measurements identifies the missing phase. For example, if L1-L2 and L2-L3 are both normal but L1-L3 is zero or very low, L2 is the problem.
  3. Check upstream fuses for that phase — Go to the upstream distribution panel and test the fuse on the affected phase. Replace if blown. Look for signs of the fault that caused the blow (discoloration, melting in the fuse holder).
  4. Inspect the input terminal at the drive — With power off and capacitors discharged (minimum 5-minute wait), inspect the terminal lug for the affected phase. It should be tight, clean, and copper-bright. Re-torque all input terminals to the specification in the ACS580 hardware manual (typically 8–12 Nm for the standard frame sizes).
  5. Inspect the upstream contactor — If fuses are good, energize the contactor and measure voltage on both sides of each contact. A contact with voltage on the upstream side but not the downstream side under load has failed.
  6. Adjust parameter 31.22 if appropriate — If input voltage quality is marginal and 3130 is causing nuisance trips, consider setting parameter 31.22 to WARNING to allow the drive to ride through brief phase imbalance events. Do not do this if the underlying phase loss is a persistent fault.
  7. Reset the drive — After restoring balanced three-phase input, press RESET on the ACS580 panel or control keypad. Confirm fault 3130 clears and monitor the DC bus voltage on startup.

Parts Often Needed

PartNotes
Input fusesMatch the type and amperage from the ACS580 hardware manual for the specific frame size
AC contactorReplace if contact inspection shows pitting or high resistance under load
Power terminal lugReplace if existing lug is corroded or cracked

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

If all three supply voltages are confirmed balanced and correct at the drive input terminals but fault 3130 persists, the rectifier input section may have been damaged by a prior phase loss event. ABB has an authorized drive repair center network for board-level diagnosis and repair. The ACS580 hardware warranty covers manufacturing defects; a phase-loss-induced rectifier failure may or may not be covered depending on the cause.

Quick FAQ

What does ABB ACS580 fault 3130 mean?

Fault 3130 (INPUT PHASE LOSS) means the drive detected a missing or severely unbalanced phase on its three-phase input supply. The ACS580 watches DC bus ripple; a lost phase produces a characteristic 2x ripple frequency, and when ripple exceeds the threshold the drive trips to protect the rectifier and DC bus capacitors.

What is the most common cause of fault 3130 on the ACS580?

A blown upstream input fuse on one phase is the most common cause. It creates a single-phase condition at the drive input. Loose L1, L2, or L3 compression lugs and burned upstream contactor contacts are the next most likely causes.

How do I find which phase is missing?

Measure phase-to-phase voltage at the drive input terminal block with the drive powered. If L1-L2 and L2-L3 read normal but L1-L3 reads zero or very low, L2 is the problem phase. Then test the upstream fuse on that phase and inspect its terminal lug and contactor contact.

Should I change parameter 31.22 to stop fault 3130?

Only if supply voltage quality is marginal and 3130 is a nuisance trip. Setting parameter 31.22 (SUPPLY PHASE LOSS) to WARNING lets the drive log A3130 and ride through brief imbalance. Do not do this if the underlying phase loss is a persistent fault.

When should I call ABB for fault 3130?

If all three supply voltages are confirmed balanced and correct at the drive input terminals but 3130 persists, the rectifier input section may have been damaged by a prior phase loss event. That needs board-level diagnosis at an ABB authorized drive repair center.


Need a professional? Compare Industrial repair options before replacing parts.