VFD-rated motor cable
First part to price when insulation damage or output-cable leakage is found.
What Siemens SINAMICS G120 Fault F30021 means, why the power unit detects a ground fault, and how to isolate the motor, cable, or brake wiring problem.
What Siemens SINAMICS G120 Fault F30021 means, why the power unit detects a ground fault, and how to isolate the motor, cable, or brake wiring problem.
Likely parts to price
First part to price when insulation damage or output-cable leakage is found.
Useful on long motor leads after true insulation faults are ruled out.
Relevant when moisture, tracking, or damaged terminals cause leakage faults.
Siemens SINAMICS G120 Fault F30021 means the power unit detected a ground fault. The drive sees leakage or a grounded condition in the motor circuit, power cable, brake circuit, or connected output components. The trip is there to protect the power module from catastrophic output-stage damage.
In the field, F30021 usually traces back to a motor winding fault, wet or damaged cable, contaminated terminal box, or brake wiring issue rather than a bad parameter.
| Part | Notes |
|---|---|
| VFD-rated motor cable | Best replacement when tray or conduit cable is leaking to ground |
| Insulation resistance tester | Essential for proving whether the motor or cable is the culprit |
| Brake resistor assembly | Relevant where the brake circuit wiring has failed |
| Output reactor / du-dt filter | Useful on long leads and can be the failed component itself |
| Replacement inverter-duty motor | Needed when megger results show winding breakdown |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Call Siemens support or a qualified drive shop if F30021 remains with the motor and downstream components disconnected. That usually points to an internal power module or sensing issue, and continued field resets can turn a repairable problem into a full drive replacement.