Siemens SINAMICS G120 F00001 Fault — Causes & Fix

2 min read

What this code means

The Siemens SINAMICS G120 F00001 fault is an overcurrent trip. The control unit has detected output current above the safe threshold for the power module, usually during startup, acceleration, or a short-circuit event. The drive shuts down immediately to protect the IGBTs and DC bus components. On G120 systems this can be caused by motor issues, cable faults, aggressive ramp settings, or a mechanical jam in the driven load.

Common Causes

Step-by-Step Fix

  1. Isolate the motor circuit — Lock out power, disconnect the motor leads, and check phase-to-phase and phase-to-ground resistance on both the cable and motor.
  2. Review commissioning parameters — Confirm motor voltage, current, frequency, and power in the G120 parameter set match the motor nameplate exactly.
  3. Increase ramp-up time — Extend the acceleration time and test again. If the trip disappears, the original ramp was too fast for the load.
  4. Check the driven machine — Turn the load manually if possible and inspect for mechanical drag, seized bearings, or a jammed conveyor, pump, or fan.
  5. Reset the system — Clear the fault through the operator panel or by cycling control power, then test with the motor uncoupled if possible to separate electrical from mechanical causes.

Parts Often Needed

PartNotes
VFD-rated motor cableAmazon | Replace if insulation is damaged or leakage to ground is found
MotorAmazon | Replace when winding insulation is weak or winding resistance is unbalanced
Siemens power module or control unitAmazon | Replace only after external motor and cable faults are ruled out

When to Call a Pro

If F00001 persists with the motor disconnected or after commissioning values are corrected, the G120 power module may be damaged internally. Siemens drive service or a qualified industrial electrician should handle module-level diagnosis and replacement.

Need this fixed instead? Describe the fault — we'll route it.

Tell us the machine and what it's doing. We read every request and reply by email. Your details go only to our dispatch inbox — see the privacy policy.

Replies come by email. Your details go only to our dispatch inbox — no account, no list.



Previous Post
Mitsubishi City Multi P8 / E6 Error Codes — Causes & Fix
Next Post
Siemens SINAMICS V20 F4 Fault — Causes & Fix