Siemens SINAMICS F30003 Fault - DC Link Undervoltage

⚡ Quick Answer

Siemens SINAMICS F30003 fault guide for DC link undervoltage, input phase loss, blown fuses, contactor drop-out, line reactors, and G120/S120 power-unit checks.

⚡ AT A GLANCEScroll down for full repair guide
What it meansF30003 means the SINAMICS power unit saw the DC link voltage fall below the allowed threshold.
Most likely causeMost siemens faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkCheck incoming phases, input fuses, contactors, line reactors, loose terminals, and DC bus readings before replacing the drive.
⏱Repair time10-45 minutes for basic checks
🔧Part neededInput fuses, line reactor, true-RMS meter, insulated torque screwdriver, and cabinet terminal hardware.
Repair intent

Need this fixed instead of diagnosed?

Siemens SINAMICS F30003 fault guide for DC link undervoltage, input phase loss, blown fuses, contactor drop-out, line reactors, and G120/S120 power-unit checks.

Parts to price first

Check the part before you book service.

VFD input fuses

Match fuse class, voltage, amp rating, and cabinet documentation before replacing a blown SINAMICS input fuse.

VFD line reactor

Use when supply dips, harmonics, or nuisance undervoltage trips point to input-side protection needs.

True RMS multimeter CAT III

Use for input phase-to-phase checks and DC bus verification by qualified personnel.

Insulated torque screwdriver

Use to retorque cabinet terminals to the documented value after lockout.

Siemens SINAMICS F30003 Fault Meaning

Siemens SINAMICS F30003 is a power-unit DC link undervoltage fault. The drive is seeing less DC bus voltage than it needs to run the inverter stage reliably.

On G120 drives, this usually points to the incoming supply, input fuses, terminals, contactor, line reactor, or PM power module. On S120 systems, it can also point to the Line Module that supplies the DC bus for the connected Motor Modules.

Jump to Checks

Common Causes

F30003 Checks {#f30003-checks}

  1. Lock out the cabinet and inspect the line side first. Look for heat marks, loose terminals, damaged fuse holders, and contactor discoloration.
  2. Verify every input fuse against the panel drawing. A single open fuse can leave the drive display alive while the DC bus collapses when the drive tries to run.
  3. Measure input voltage phase to phase at the drive input with a rated meter. Compare L1-L2, L2-L3, and L1-L3 instead of trusting one reading.
  4. Watch whether the fault happens at power-up, run command, acceleration, or when another machine starts. Timing often separates facility supply dips from drive hardware failure.
  5. Check the contactor and safety chain. A contactor that drops for a split second can create F30003 even when static voltage readings look normal.
  6. If the incoming power stays stable, check the DC bus reading in Startdrive, STARTER, the BOP-2, or the machine HMI. Use qualified personnel only because DC bus work is hazardous.
  7. Back up parameters before replacing a power module, Line Module, or Control Unit.

What to Check by System

SystemF30003 focus
SINAMICS G120 / G120CInput fuses, incoming phase loss, PM terminals, line reactor, main contactor
SINAMICS S120Line Module status, DC bus supply, input fuses, DRIVE-CLiQ fault context
SINUMERIK CNC with S120Full 25xxx alarm text plus the underlying SINAMICS drive fault
Pump or fan panelsUtility dips, soft power loss, contactor chatter, and undersized feeder

Parts and Tools

F30003 is usually an input-power diagnosis before it is a drive replacement. Start with verified fuses, a rated meter, and cabinet hardware that matches the panel documentation. Do not replace a SINAMICS power module until the incoming supply and DC bus behavior have been documented.

Quick FAQ

What does Siemens SINAMICS F30003 mean?

F30003 means the SINAMICS power unit detected DC link undervoltage. On G120 and S120 systems, start with incoming supply, input fuses, phase loss, contactor drop-out, and DC bus measurements before suspecting the power module.

Can I reset a Siemens F30003 fault?

A reset may clear F30003 after a brief supply dip. If the fault returns, verify all input phases and the DC bus under load before repeated resets hide a blown fuse, weak contactor, or supply problem.

Does F30003 mean the SINAMICS drive is bad?

Not by itself. Many F30003 trips are caused by upstream power loss, a missing phase, loose terminals, failing fuses, contactor chatter, or facility voltage dips. Suspect the power unit only after the incoming supply remains stable.


Need a professional? Compare Industrial repair options before replacing parts.