Siemens G120C VFD Fault Codes

⚡ Quick Answer

Siemens G120C guide for F00001, F00002, F00003, F00004, F30001, drive cooling, motor wiring, braking, and BOP-2 checks.

⚡ AT A GLANCEScroll down for full repair guide
What it meansSiemens G120C guide for F00001, F00002, F00003, F00004, F30001, drive cooling, motor wiring, braking, and BOP-2 checks.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededDrive cooling fan
Repair intent

Need this fixed instead of diagnosed?

Siemens G120C guide for F00001, F00002, F00003, F00004, F30001, drive cooling, motor wiring, braking, and BOP-2 checks.

Likely parts to price

Price the common parts before you book service.

Drive cooling fan

Common heat-related VFD and servo-drive failure point.

Keypad operator panel

Useful when the drive display or controls fail.

Braking resistor

Price this on braking, deceleration, and overvoltage faults.

Siemens G120C VFD Fault Codes — What They Mean

The Siemens SINAMICS G120C is a compact variable frequency drive in the G120 product family. The G120C integrates the Control Unit and Power Module into a single compact housing, making it ideal for space-constrained panel installations in pumps, fans, and simple conveyor applications. It uses the same SINAMICS fault code structure as the G120 modular series — faults are prefixed with “F” and alarms with “A.” Codes are displayed on the Basic Operator Panel (BOP-2) or the Intelligent Operator Panel (IOP).

Jump to Fix

Siemens G120C Common Fault Code Reference

Fault CodeDescription
F00001Overcurrent — drive output current exceeded limit
F00002Overvoltage — DC link voltage too high
F00003Undervoltage — DC link voltage too low
F00004Drive overtemperature — heatsink temp exceeded
F00005Drive I²t overload
F00011Motor overtemperature — PTC/NTC sensor
F00021Ground fault detected
F00030Drive hardware fault
F00051EEPROM fault — parameter storage error
F00052Power stack fault
F00070CB30B communication board fault
F00071PROFIBUS/PROFINET communication fault
F00076PID feedback sensor fault
F00090Encoder fault (where encoder is fitted)
F01003Motor phase loss

Common Causes by Fault

Step-by-Step Fix

  1. Read the fault — The BOP-2 or IOP displays the fault code (e.g., “F00001”) and a brief text description. Use the navigation buttons to display more detail. The fault buffer (parameter r0945) stores up to 8 fault codes with timestamps.
  2. For F00001 (overcurrent) — Check the driven load — try turning it manually. If it won’t turn freely, the mechanical issue must be resolved first. Review acceleration time parameter P1120 — increase it by 50% and retry. Also check motor cable for any shorts between conductors.
  3. For F00004 (overtemperature) — Check the G120C cooling fan (audible when drive is powered). Confirm ambient temperature at the drive location is below 40°C (104°F). Check panel ventilation — drives mounted in sealed panels frequently overheat.
  4. For F00021 (ground fault) — Disconnect motor cable at the drive terminals. Measure insulation resistance from each motor lead to ground with a 500V megohmmeter — should be greater than 1 MΩ. A reading below 1 MΩ indicates a cable or motor winding fault.
  5. Clear and restart — After resolving the fault cause, press the FAULT RESET button on the BOP-2 (or use the reset command via PROFIBUS). The G120C does not auto-restart — a reset must be commanded.

Parts Often Needed

PartNotes
G120C internal cooling fanReplacement fan for thermal fault prevention
BOP-2 operator panelFor local diagnostics and parameter access
PROFIBUS connector9-pin D-sub with built-in EOL resistor
Motor PTC thermistorFor F00011; check PTC resistance (normal: 100–1000 Ω)
Complete G120C driveFor F00030 or F00052 hardware faults

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Siemens G120C drives can be remotely diagnosed via PROFINET using Siemens STARTER or TIA Portal. If the drive is integrated into a PROFINET network, a Siemens-trained automation technician can view the full fault buffer, drive telemetry, and parameter settings without being physically at the drive. For F00030 (hardware fault), contact Siemens technical support or a Siemens Service Partner.