What Schneider Altivar OCF fault means, why overcurrent trips the drive, and how to fix it.
OCF (Overcurrent Fault) on a Schneider Altivar drive (ATV12, ATV320, ATV630, ATV930) indicates that the output current exceeded the instantaneous overcurrent trip threshold — typically 200–300% of the drive’s rated current depending on the model. OCF is a fast hardware-level protection; it trips in microseconds (unlike OLF which is thermal and time-delayed) to prevent IGBT destruction from a hard short or sudden mechanical overload.
| Part | Notes |
|---|---|
| Motor cable (VFD-rated, screened) | Replace if insulation test fails |
| Motor (replacement or rewind) | If winding short circuit is confirmed |
| Drive output filter (dV/dt) | Reduces cable stress on long runs |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If the drive itself trips OCF with no output connected, the internal IGBT or driver card has failed. Drive internal repair requires Schneider-authorized service or drive replacement. Always follow lockout/tagout procedures before testing output circuits.