Drive cooling fan
Common heat-related VFD and servo-drive failure point.
Diagnose Lenze VFD Fault LP - Causes & Fix: likely causes to check, measurements to verify, and repair decisions before parts replacement.
Likely parts to price
Common heat-related VFD and servo-drive failure point.
Useful when the drive display or controls fail.
Price this on braking, deceleration, and overvoltage faults.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
Diagnose Lenze VFD Fault LP - Causes & Fix: likely causes to check, measurements to verify, and repair decisions before parts replacement.
Lenze fault LP (Phase Loss) indicates the drive detected a missing or severely unbalanced input phase on its 3-phase AC supply. On Lenze 8200, 9300, and i550 series drives, the rectifier monitors all three input phases (L1, L2, L3); if one phase is absent or drops significantly below the others, LP is triggered and the drive shuts down to prevent DC bus ripple damage and overloading the remaining input phases. Single-phase operation of a 3-phase drive can destroy the rectifier diodes within minutes.
| Part | Notes |
|---|---|
| Input fuses | Match voltage, amperage, and fuse class exactly (often aR or gG type on European drives) |
| Input line contactor | If contact burning is confirmed; match coil voltage and current rating |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If all three input phases measure correctly at the drive terminals but LP persists, the drive’s rectifier or input phase loss detection circuit may have failed. Lenze rectifier replacement requires drive board disassembly — contact a Lenze service center or certified integrator.