Control Techniques Unidrive SP Fault Codes — Complete Guide

⚡ Quick Answer

Unidrive SP fault codes identify DC bus, encoder, motor, braking, thermal, and communication trips on Control Techniques drives.

⚡ AT A GLANCEScroll down for full repair guide
What it meansControl Techniques Unidrive SP trip codes separate output overcurrent, DC bus overvoltage or undervoltage, heatsink and board temperature, motor thermal, serial communication, EEPROM, encoder, input phase loss, and ground-fault conditions.
Most likely causeCommon causes include short acceleration or deceleration ramps, high-inertia loads, shorted motor wiring, missing input phases, blocked heatsinks, failed cooling fans, hot panels, interrupted fieldbus wiring, parameter corruption, encoder signal loss, or motor and cable insulation breakdown.
First checkRead Pr 10.20 through Pr 10.29 before resetting, then match the trip to the drive state: OI.AC points to load or motor wiring, OV points to regenerative braking, OH points to cooling, SCL points to communications, and GF points to insulation testing.
⏱Repair time15-45 minutes for history, parameter, fuse, wiring, fan, and cabinet-airflow checks; 1-3 hours for braking resistor, encoder, motor-cable, fieldbus module, or drive replacement decisions.
🔧Part neededUnidrive SP braking resistor, cooling fan, keypad, fieldbus option module, encoder cable, input fuses, motor insulation tester.
Repair intent

Need this fixed instead of diagnosed?

Unidrive SP fault codes identify DC bus, encoder, motor, braking, thermal, and communication trips on Control Techniques drives.

Parts to price first

Check the part before you book service.

Unidrive SP braking resistor

Use only when OV trips are tied to rapid deceleration or high-inertia loads after checking decel parameters.

Unidrive SP cooling fan

Match the fan to the exact drive frame before replacing it for OH heatsink temperature trips.

Control Techniques keypad

Use for damaged displays or buttons that prevent trip history review and parameter access.

Motor insulation tester

Use a megohmmeter to separate GF trips caused by motor or cable insulation from drive output faults.

Control Techniques Unidrive SP Fault Codes — Quick Reference

Control Techniques (now part of Nidec) manufactures the Unidrive SP and Unidrive M series variable-speed drives, widely used in industrial applications. The drives display fault codes as text “trip” codes on the keypad display. The trip history is accessible via parameter Pr 10.20–10.29 (last 10 trips).

Trip CodeMeaningCommon CauseQuick Fix
OI.ACOvercurrent — AC outputShort circuit; too fast accelerationCheck motor wiring; increase accel time
OI.DCOvercurrent — DC busBraking energy; voltage spikeAdd brake resistor; check decel
OVDC Bus OvervoltageFast deceleration; high supply voltageIncrease decel time; add brake resistor
UVDC Bus UndervoltageLow input voltage; power interruptionCheck supply voltage; check fuses
OHDrive heatsink overtemperatureBlocked fan; high ambient tempClean heatsink; improve ventilation
OH2Control board overtemperatureAmbient too hotImprove enclosure cooling
t.dEFThermistor fault — motor PTCPTC resistance out of rangeCheck PTC wiring; check motor temp
OtMotor overtemperature — model-basedMotor overloadedReduce load; check motor cooling
SCLSerial comms lossFieldbus or serial link interruptedCheck comms wiring; check master device
EEFEEPROM fault — parameter errorParameter corruptionRestore factory defaults and reprogram
PSFPower supply fault — internalInternal power supply failedReplace drive
O.SPdOverspeedSpeed feedback exceeded limitCheck speed reference; check encoder
EnCEncoder faultEncoder signal lost or invalidCheck encoder wiring; check speed
PhInput phase lossMissing L1, L2, or L3Check input wiring; check fuses
GFGround faultMotor or cable insulation faultMegger motor; check cable

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Most Common Faults

OI.AC — AC Output Overcurrent

The output current exceeded the instantaneous trip threshold (typically 200–220% of rated current). This is the most common trip on the Unidrive SP in industrial pump and fan applications.

Diagnosis:

  1. Check if the trip occurs at startup or while running — startup OI.AC often indicates too-short acceleration time or a high-inertia load
  2. If running, check for a mechanical jam in the driven load
  3. Disconnect the motor and check output wiring for short circuits between phases or phase-to-ground

Fix:

OV — DC Bus Overvoltage

Occurs when regenerated energy from rapid deceleration raises the DC bus voltage above the trip threshold (typically 830VDC on 400VAC drives, 415VDC on 200VAC drives).

Fix:

OH — Heatsink Overtemperature

The Unidrive SP uses forced-air cooling via an internal fan. The heatsink trip occurs at approximately 90°C.

Fix:

  1. Clean the heatsink fins thoroughly — the fins on the back of the drive pack with dust rapidly in industrial environments
  2. Verify the internal cooling fan is running — it should be audible when the drive is powered
  3. Check ambient temperature in the panel: maximum for Unidrive SP is 40°C
  4. Verify minimum clearances: 100mm above, 100mm below, and 30mm on sides (or per installation guide)

SCL — Serial Communications Loss

The drive lost contact with its Fieldbus master (PROFIBUS, EtherNet/IP, Modbus RTU, etc.) or serial link. Check the communications cable, the module connector on the drive, and the scan rate settings. Verify the master device is polling the drive.

EEF — EEPROM Fault

Parameter memory has corrupted. This can occur after a power interruption during a parameter save. Reset to factory defaults (Pr 00.09 = 1000 for most models), then reprogram all required parameters. Save all parameters to a computer before this reset if possible using CT’s SyPTPro or Connect software.

Unidrive SP Parameter Menu Access

When to Call a Pro

PSF (internal power supply), GF (ground fault with motor failure), and Ph (input phase loss) on a persistent basis require an industrial drive specialist. Control Techniques service centers offer drive repair and board-level service.

Quick FAQ

What is the first thing to check on a Unidrive SP fault?

Read the trip history in Pr 10.20 through Pr 10.29 before pressing reset. The same trip means different things if it happened during acceleration, deceleration, steady running, or power-up.

What causes OI.AC on a Control Techniques Unidrive SP?

OI.AC is AC output overcurrent. Common causes are a short acceleration ramp, mechanical binding, incorrect motor data, a shorted motor lead, or a motor and cable insulation problem.

How do I stop OV faults on a Unidrive SP?

Increase deceleration time first, then enable voltage-dependent deceleration if the application allows it. High-inertia loads that must stop quickly may need a correctly sized braking resistor.

When should a Unidrive SP be replaced?

Do not replace the drive until input power, motor wiring, motor insulation, cooling, parameters, and external braking are checked. Persistent PSF faults or GF trips with the motor disconnected need drive service.


Need a professional? Compare Industrial repair options before replacing parts.