Danfoss VFD Fault AL 14 - Ground Fault Fix

⚡ Quick Answer

Diagnose Danfoss VFD AL 14 ground faults: motor insulation tests, output-cable checks, drive isolation, and repair decisions.

⚡ AT A GLANCEScroll down for full repair guide
What it meansDiagnose Danfoss VFD AL 14 ground faults: motor insulation tests, output-cable checks, drive isolation, and repair decisions.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededVFD-rated motor cable
Repair intent

Need this fixed instead of diagnosed?

Diagnose Danfoss VFD AL 14 ground faults: motor insulation tests, output-cable checks, drive isolation, and repair decisions.

Likely parts to price

Price the common parts before you book service.

VFD-rated motor cable

First part to price when insulation damage or output-cable leakage is found.

Output line reactor

Useful on long motor leads after true insulation faults are ruled out.

Motor terminal kit

Relevant when moisture, tracking, or damaged terminals cause leakage faults.

Danfoss VFD Fault AL 14 — What It Means

Danfoss alarm AL 14 is a Ground Fault — the drive detected significant current leaking from one or more output phases to earth ground. On Danfoss FC-series drives (FC51, FC100, FC200, FC300, FC360), the drive monitors the sum of all three output phase currents; in a healthy system, the vector sum equals zero. When the sum is non-zero (current is flowing to ground), AL 14 trips the drive to protect personnel and equipment from ground fault hazards. Ground faults most commonly originate in the motor winding insulation or the output power cable.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Isolate the motor — Apply LOTO. Disconnect the motor cable at the drive’s U/V/W output terminals. Attempt to reset the fault (power cycle or reset button).
  2. Test with motor disconnected — If AL 14 clears with the motor disconnected, the fault is in the motor or the output cable — not the drive itself.
  3. Megger (insulation resistance) test the motor — With the motor disconnected and cold, use a 500V or 1000V megohmmeter to measure insulation resistance between each motor terminal (U, V, W) and the motor frame/ground. A healthy motor reads >1 MΩ (ideally >100 MΩ). Below 1 MΩ indicates compromised insulation.
  4. Megger test the output cable — With both ends disconnected, test insulation resistance from each conductor to the cable’s outer jacket or shield. Values below 1 MΩ indicate damaged cable insulation.
  5. Test the drive with a different motor/cable — If available, connect a known-good motor on a short temporary cable. If AL 14 doesn’t trip, the original motor or cable is the fault source.
  6. Clear and return to service — After repairs, reconnect the verified good motor/cable, power cycle the drive, and confirm AL 14 doesn’t recur during a low-speed test run.

Parts Often Needed

PartNotes
Motor (rewound or replacement)If insulation resistance is below 1 MΩ
Output power cableShielded, rated for VFD output; replace if megger test shows insulation damage

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

If AL 14 persists with the motor disconnected, the drive itself has a faulty output stage. Danfoss IGBT replacement requires specialized soldering and testing equipment. Contact Danfoss service or a certified drive repair shop — do not attempt internal drive repair without proper training.


Need a professional? Compare Industrial repair options before replacing parts.