Diagnose Danfoss VFD AL 14 ground faults: motor insulation tests, output-cable checks, drive isolation, and repair decisions.
Likely parts to price
First part to price when insulation damage or output-cable leakage is found.
Useful on long motor leads after true insulation faults are ruled out.
Relevant when moisture, tracking, or damaged terminals cause leakage faults.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
Diagnose Danfoss VFD AL 14 ground faults: motor insulation tests, output-cable checks, drive isolation, and repair decisions.
Danfoss alarm AL 14 is a Ground Fault — the drive detected significant current leaking from one or more output phases to earth ground. On Danfoss FC-series drives (FC51, FC100, FC200, FC300, FC360), the drive monitors the sum of all three output phase currents; in a healthy system, the vector sum equals zero. When the sum is non-zero (current is flowing to ground), AL 14 trips the drive to protect personnel and equipment from ground fault hazards. Ground faults most commonly originate in the motor winding insulation or the output power cable.
| Part | Notes |
|---|---|
| Motor (rewound or replacement) | If insulation resistance is below 1 MΩ |
| Output power cable | Shielded, rated for VFD output; replace if megger test shows insulation damage |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If AL 14 persists with the motor disconnected, the drive itself has a faulty output stage. Danfoss IGBT replacement requires specialized soldering and testing equipment. Contact Danfoss service or a certified drive repair shop — do not attempt internal drive repair without proper training.