York 10K temperature sensor
Part: S1-02525919700
Sensor part listed for YSC E2, E3, and E4 temperature faults.
Complete York YSC series rooftop unit error codes. Covers all E-codes, P-codes, and flash codes with technician-level diagnostic steps.
Complete York YSC series rooftop unit error codes. Covers all E-codes, P-codes, and flash codes with technician-level diagnostic steps.
Parts to price first
Part: S1-02525919700
Sensor part listed for YSC E2, E3, and E4 temperature faults.
Model-specific igniter category listed for ignition lockouts.
Flame-sensing part listed for flash 7 flame-sense faults.
Switch category listed for E6 and E7 high-pressure lockouts.
Capacitor category listed for condenser fan and blower diagnosis.
Board category listed for communication and control faults; match by unit model.
The York YSC series is a light commercial packaged rooftop unit covering 2–12.5 tons. Fault codes are displayed via the LED on the IFC board (flash codes) and alphanumeric codes on the optional diagnostic panel or communicating thermostat.
| Flash Count | Fault | Common Cause |
|---|---|---|
| 1 flash | System lockout | Manual reset required |
| 2 flashes | Low-pressure switch open | Low refrigerant, dirty filter |
| 3 flashes | High-pressure switch open | Dirty condenser, fan failure |
| 4 flashes | Limit switch open | Airflow restriction |
| 5 flashes | Rollout switch open | Heat exchanger issue |
| 6 flashes | Ignition lockout | Gas, igniter, or sensor fault |
| 7 flashes | Flame sense fault | Dirty or failed flame sensor |
| 8 flashes | Pressure switch stuck closed | Faulty pressure switch |
| 9 flashes | Reverse rotation — blower | Blower wired incorrectly or failed |
| Code | Description | Likely Cause / Action |
|---|---|---|
| E1 | Control board communication fault | Check wiring harness, replace board |
| E2 | Supply air temperature sensor fault | Check sensor resistance, replace |
| E3 | Return air temperature sensor fault | Check or replace return sensor |
| E4 | Outdoor air temperature sensor fault | Check or replace outdoor sensor |
| E5 | Discharge temperature sensor fault | Check sensor at compressor discharge |
| E6 | High-pressure switch lockout — circuit 1 | Check condenser coil, fan, refrigerant |
| E7 | High-pressure switch lockout — circuit 2 | Check condenser coil, fan, refrigerant |
| E8 | Low-pressure switch lockout | Check refrigerant charge and airflow |
| E9 | Compressor time delay active | Wait — normal startup protection |
| P1 | Low-ambient compressor lockout | Ambient below minimum — check settings |
| P2 | Low-ambient heating lockout | Ambient too low for heating operation |
| P3 | Brownout / low voltage lockout | Check supply voltage |
| H1 | High humidity lockout | Dehumidification mode — check controls |
The most frequent YSC summer fault:
The most frequent YSC heating fault:
Temperature sensors on York YSC units have a nominal resistance of 10K ohms at 77°F (25°C). Check resistance with a multimeter and compare to the resistance chart in the service manual.
| Part | Notes |
|---|---|
| Temperature sensor | 10K thermistor — York part S1-02525919700 |
| Hot surface igniter | Model-specific — check tonnage and model suffix |
| Flame sensor rod | Measure µA before replacing |
| High-pressure switch | Check trip pressure setting |
| Run capacitor | Check µF on both compressor and fan caps |
| IFC control board | York part number varies by tonnage |
York YSC rooftop units can report both heating and cooling faults from the same control system, so do not stop at the first flash count. Record whether the call was for heat, cooling, or fan-only operation, then check the matching side of the unit: condenser fan and pressure switches for E6/E7 cooling trips, blower airflow and limits for heat trips, and sensor resistance for E2 through E5 faults.
DIY vs Pro: Filter changes, coil cleaning, visual wiring checks, and sensor resistance checks are reasonable for a skilled maintenance tech. Gas valve work, refrigerant diagnosis, compressor faults, and rooftop electrical work should go to a licensed commercial HVAC contractor.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Note: The York YSC shares many components with the Coleman and Luxaire commercial RTU lines. Parts are interchangeable.