Carrier WeatherMaker Rooftop Unit Error Codes

Carrier WeatherMaker 48/50 Series RTUs use an LED diagnostic board that flashes fault codes. Count the LED flashes, wait for a 3-second pause, and count again. The total equals the fault code. Some newer units display codes on a 7-segment display.

WeatherMaker Flash Code Table

CodeFault DescriptionCommon CauseAction
2Low-pressure lockoutLow refrigerant, dirty evaporator coilCheck static pressure, inspect filter
3High-pressure lockoutDirty condenser coil, failed condenser fanWash coil, check fan rotation
11Ignition failureNo gas, weak spark, dirty flame sensorCheck gas pressure (3.5 in. w.c.)
12Flame sense faultDirty or cracked flame sensorClean or replace flame sensor rod
13Limit switch openRestricted airflow, dirty filterReplace filter, check blower wheel
14Ignition lockout3 failed ignition attemptsManual reset required
21Gas valve faultFailed gas valve or wiring issueCheck 24 VAC at gas valve
22Low combustion airBlocked flue, failed inducerInspect flue and inducer pressure
23Draft safeguard switchBlocked flue or failed inducer motorMeasure inducer manifold pressure
31High-pressure switch openRefrigerant overcharge, blocked condenserCheck subcooling (10–15°F target)
33Limit switch lockoutPersistent overtemperatureFix airflow restriction before reset
41Blower motor faultFailed blower motor or run capacitorCheck capacitor ┬╡F, motor amps
42Inducer motor faultFailed inducer motor or blocked flueCheck inducer amp draw
44Control board faultInternal board failureReplace IFC board
46Power failurePower interruption detectedCheck supply voltage and breakers

Most Common WeatherMaker Faults

Code 13 — Limit Switch Open

The top commercial RTU call. Work through in order: replace dirty filter, verify all grilles are open, inspect blower wheel for debris, then check limit switch continuity at room temperature.

Code 23 — Draft Safeguard Switch

Measure inducer manifold pressure before condemning the pressure switch. Typical WeatherMaker spec is -0.20 to -0.35 in. w.c. at the pressure switch. A blocked flue screen is a common culprit.

Code 11 — Ignition Failure

Check gas pressure first. Natural gas inlet pressure must be 5–7 in. w.c.; manifold pressure 3.5 in. w.c. Clean the flame sensor rod with steel wool — measure ┬╡A (must exceed 1.5 ┬╡A).

Code 3 — High Pressure

Verify all condenser fan motors are running and drawing rated amps. Wash the condenser coil. Check refrigerant subcooling with manifold gauges.

Parts Commonly Needed

PartNotes
Flame sensor rodAmazon | Clean first; replace if ┬╡A reading is below 1.5
IFC boardAmazon | Model-specific — cross-reference part number
Limit switchAmazon | Match temperature rating exactly
Run capacitorAmazon | Test ┬╡F with capacitor tester before condemning motor
Inducer motorAmazon | Check capacitor before replacing motor
Pressure switchAmazon | Verify switch spec matches flue pressure measured

Pro tip: Carrier WeatherMaker IFC boards store the last 5 fault codes. Hold the diagnostic button 5 seconds to retrieve fault history before clearing codes.