York RTU hot surface igniter
Match the RTU model, connector, mounting bracket, and igniter style before replacing ignition lockout faults.
York RTU error-code guide for Predator, Affinity, and ZF rooftop units, including pressure lockouts, ignition faults, flame-sense errors, sensors, and blower faults.
York RTU error-code guide for Predator, Affinity, and ZF rooftop units, including pressure lockouts, ignition faults, flame-sense errors, sensors, and blower faults.
Parts to price first
Match the RTU model, connector, mounting bracket, and igniter style before replacing ignition lockout faults.
Clean and microamp-test the existing rod before replacing flame-sense faults.
Match high-side or low-side setting, tubing, and switch rating after proving the pressure condition.
Check microfarads and voltage rating before replacing blower or condenser fan capacitor faults.
York commercial RTUs (Predator, Affinity, ZF, YCIV series) use LED flash codes and alphanumeric displays to communicate faults. York RTU equipment is also sold under the Luxaire and Coleman commercial brands with identical codes.
The IFC diagnostic LED flashes codes in groups:
| Flash Code | Fault | Common Cause |
|---|---|---|
| 2 | Low-pressure lockout | Low refrigerant charge |
| 3 | High-pressure lockout | Dirty condenser coil, fan failure |
| 4 | Limit switch open | Airflow restriction, dirty filter |
| 5 | Rollout switch open | Cracked heat exchanger, blocked burner |
| 6 | Ignition lockout | No ignition after 3 attempts |
| 7 | Flame signal lost | Dirty or failed flame sensor |
| 8 | Blower motor fault | Motor or capacitor failed |
| 2-2 | Low-pressure switch stuck closed | Replace pressure switch |
| 3-3 | High-pressure switch stuck closed | Replace pressure switch |
| 4-1 | Primary limit fault | Overtemperature — check airflow |
| 4-2 | Secondary limit fault | Overtemperature — check secondary limit |
| 5-1 | Gas valve fault | Check valve and wiring |
| 6-1 | Inducer fault | Check inducer motor and flue |
| Code | Description | Action |
|---|---|---|
| E1 | Control board communication fault | Check wiring, replace board |
| E2 | Supply air sensor open/shorted | Check sensor resistance |
| E3 | Return air sensor fault | Check or replace sensor |
| E4 | Outdoor sensor fault | Check or replace outdoor sensor |
| E6 | High-pressure lockout — compressor 1 | Check condenser, coil, charge |
| E7 | High-pressure lockout — compressor 2 | Check condenser, coil, charge |
| E8 | Low-pressure lockout | Check refrigerant charge |
| P1 | Low-ambient compressor lockout | Ambient below min — check lockout settings |
| P2 | Low-ambient heating lockout | Ambient below heating minimum |
Dirty filter is the number-one cause. Check:
| Part | Notes |
|---|---|
| Hot surface igniter | Silicon carbide — handle with gloves |
| Flame sensor | Measure µA output; replace below 1.5 µA |
| Limit switch | Match temperature rating |
| Run capacitor | Check µF before condemning motor |
| Pressure switch | High or low side — match setting |
| IFC board | York part number varies by model year |
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Note: York, Luxaire, and Coleman commercial RTUs share the same IFC control boards and fault codes. Parts are fully interchangeable across brands.
York RTU flash codes usually point to pressure lockouts, limit faults, rollout faults, ignition lockout, flame-sense loss, blower faults, or high and low pressure switch problems.
Check the hot surface igniter, flame sensor, gas pressure, rollout switches, venting, and ignition wiring before replacing the IFC board.
Many York, Luxaire, and Coleman commercial RTUs share Johnson Controls platforms, but parts still need to match the full model, serial, voltage, and control-board revision.