Troubleshoot Yaskawa GF on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Troubleshoot Yaskawa GF on VFD drives with checks for input power, motor wiring, load, cooling, parameters, and likely replacement parts.
Likely parts to price
Common heat-related VFD and servo-drive failure point.
Useful when the drive display or controls fail.
Price this on braking, deceleration, and overvoltage faults.
Yaskawa fault GF means ground fault — the drive detected that output current is flowing to ground rather than returning through the motor windings normally. On Yaskawa V1000, A1000, and GA700 drives, GF is detected by comparing the sum of currents on all three output phases; in a normal motor circuit, they sum to zero. When a ground fault exists, current leaks to ground and the three-phase sum is non-zero. The drive trips immediately to protect both the motor and personnel from dangerous ground current. GF is almost always caused by damaged motor winding insulation or a damaged output cable.
| Part | Notes |
|---|---|
| Motor (replacement) | Required if winding insulation tests below acceptable threshold |
| VFD-rated output cable (shielded) | Replace if any conductor shows insulation damage |
| Output reactor (line choke) | Install if GF is caused by long cable capacitive leakage |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Megohm meter testing and motor insulation analysis requires proper equipment and safety procedures. If the motor tests marginal (500 kΩ to 1 MΩ), a motor shop can do a more thorough surge test and rewinding assessment.