Yaskawa GA700 semiconductor input fuses
Match voltage class, amp rating, fuse class, and the GA700 manual before replacing a blown input fuse tied to UV1.
Yaskawa GA700 Fault UV1 - Main Circuit Undervoltage Causes & Fix: likely causes, checks, and repair decisions before replacing parts.
Yaskawa GA700 Fault UV1 - Main Circuit Undervoltage Causes & Fix: likely causes, checks, and repair decisions before replacing parts.
Parts to price first
Match voltage class, amp rating, fuse class, and the GA700 manual before replacing a blown input fuse tied to UV1.
Use when repeated UV1 events trace to phase loss, brownouts, or unstable plant supply rather than the drive.
Size by drive current and voltage when adding input protection for supply sag or transient-heavy panels.
Use for R/S/T line-voltage checks before condemning the GA700 soft-charge circuit or capacitor bank.
UV1 on a Yaskawa GA700 drive (GA700 = Yaskawa’s heavy-duty industrial drive platform, successor to the A1000) indicates Main Circuit Undervoltage — the DC bus voltage has dropped below the minimum operating level. The GA700 monitors the DC bus continuously and trips UV1 when the bus falls below approximately 190 VDC on 200 V class drives or 380 VDC on 400 V class drives. UV1 is a protective fault; running the drive on an undervoltage bus would cause output waveform distortion, increased motor heating, and possible damage to the drive’s capacitors and power devices.
| Part | Notes |
|---|---|
| Input fuses (semiconductor) | Use Yaskawa-specified fuse type for GA700 ampere rating |
| Soft-charge relay or thermistor | GA700 frame-size specific; order from Yaskawa |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, voltage class, amp rating, and confirmed input-power fault. Check current prices on Amazon - prices and availability change frequently.
UV1 on a GA700 driving a large motor (over 30 kW) should be investigated by a qualified drive technician. Incorrect supply voltage or a failing capacitor bank on a large drive can cause dangerous fault-trip energy releases during reset attempts.
UV1 means the GA700's main DC bus voltage dropped below the drive's minimum operating threshold. Start with incoming power, input fuses, phase loss, and fault history before replacing drive hardware.
Yes. One open input fuse or contactor pole can pull the rectified DC bus down enough to trip UV1, so check all three phases at the drive input.
Only after proving the supply is stable, all input phases are present, fuse and breaker hardware are good, and UV1 still appears at startup or under normal load.