LG Window AC CH05 Error Code - Condenser Thermistor Fault: likely causes, checks, and repair decisions before replacing parts.
LG Window AC CH05 Error Code - Condenser Thermistor Fault: likely causes, checks, and repair decisions before replacing parts.
Likely parts to price
Common error-code part. Confirm resistance and connector style.
Useful to price for temperature-reading faults.
Low-cost safety part for heat and no-start symptoms.
Your LG window air conditioner is displaying CH05, which means the condenser coil temperature sensor (a secondary thermistor) has failed or is reading out of range. While CH01 tracks the room air temperature, CH05 tracks the temperature of the outdoor coils — the condenser.
When this sensor fails, the control board doesn’t know if the condenser is at a safe operating temperature. It shuts down the compressor as a safety precaution. The unit may run the fan but won’t produce cold air.
This is slightly more involved than the CH01 fix because the condenser thermistor is located near the hot, dirty outdoor section of the unit. But with the right approach, you can still fix it yourself.
| Code | Meaning | Severity | DIY Fix? |
|---|---|---|---|
| CH05 | Condenser coil thermistor fault | Moderate | Yes — clean and test, then replace if needed |
Before blaming the sensor, take a good look at the condenser coils (the outdoor fins on the back of the window AC). A blocked or heavily dirty condenser can overheat and trip the CH05 code even if the sensor itself is fine. The control board sees a temperature that’s too high and flags it as a sensor fault.
If the coils are dirty, move to Fix 2. If they’re clean, skip to Fix 3.
A thorough coil cleaning often clears CH05. This is basic maintenance every window AC needs anyway.
Once dry, plug in and test. If CH05 is gone, you just needed a spring cleaning. If not, the thermistor itself is likely bad.
If cleaning didn’t help, it’s time to test the sensor. You’ll need a multimeter.
If you get OL (open loop), 0Ω, or a fixed reading that doesn’t change when you warm the bead with your fingers, the thermistor is bad.
If the test confirms a bad sensor, replacement is the fix.
If the compressor kicks on and stays on, the fix worked.
If you’ve cleaned the coils and replaced the thermistor but CH05 persists, the sensor circuit on the control board may be damaged. This is rare with LG window ACs but possible after a power surge.
Given that a replacement window AC costs $150–$500, a control board swap only makes financial sense on larger units. If your AC is a small model (under 8,000 BTU), do the math before buying.
CH05 is often a maintenance code in disguise. A clean condenser coil runs cooler, and a cooler coil puts less stress on the thermistor and compressor.