Kaeser oil separator element
Match the compressor package model before replacing a clogged separator element for differential-pressure faults.
Kaeser SIGMA CONTROL 2 fault-code guide for compressor warnings, shutdowns, final-temperature trips, pressure sensors, service resets, and dryer alarms.
Kaeser SIGMA CONTROL 2 fault-code guide for compressor warnings, shutdowns, final-temperature trips, pressure sensors, service resets, and dryer alarms.
Parts to price first
Match the compressor package model before replacing a clogged separator element for differential-pressure faults.
Use the exact package model and service kit reference when the SIGMA CONTROL 2 service interval calls for oil-filter replacement.
Part: 4-20 mA
Confirm pressure range, thread, connector, and 4-20 mA signal before replacing a pressure sensor fault.
Match the sensor type and resistance curve before replacing a temperature sensor fault.
Kaeser compressors with SIGMA CONTROL 2 use text-based alarm messages displayed on the controller panel. The SIGMA CONTROL 2 provides more detail and connectivity than the original Sigma Control, including Ethernet integration and remote monitoring via SIGMA NETWORK. If a search or work order says “Kaeser compressor fault code 2,” verify that it is referring to the controller generation before treating “2” as a fault number.
| Alarm Message | Category | Common Cause | Action |
|---|---|---|---|
| Final compression temp - Warning | Warning | Approaching high temp limit | Clean coolers, check oil |
| Final compression temp - Shutdown | Shutdown | Excessive temperature | Clean coolers, check oil, check ambient |
| Motor protection - Shutdown | Shutdown | Motor overload | Check motor amps and load |
| Emergency stop - Active | Shutdown | E-stop circuit open | Check all E-stop switches |
| Pressure sensor - Fault | Warning | Failed pressure transducer | Check sensor wiring and signal |
| Temperature sensor - Fault | Warning | Failed temperature sensor | Check sensor resistance |
| Dryer - Fault | Warning | Integrated dryer alarm | Check refrigerant dryer operation |
| Service - Required | Maintenance | Service interval reached | Perform scheduled service |
| Fan motor - Fault | Shutdown | Cooling fan motor fault | Check fan motor amps and contactor |
| Condensate drain - Fault | Warning | Drain solenoid not operating | Check drain solenoid and timer |
| Oil filter - Service | Maintenance | Oil filter replacement due | Replace oil filter element |
| Differential pressure - High | Warning | Separator element clogged | Replace separator element |
| Communication - Fault | Warning | Network communication loss | Check Ethernet and network config |
| Phase - Fault | Shutdown | Phase loss or reversal | Check input power quality |
Kaeser’s shutdown threshold is typically 110 degrees C (230 degrees F). Warning precedes shutdown by approximately 5 degrees C. Root cause is almost always a dirty cooler. Kaeser SIGMA CONTROL 2 logs the temperature trend - review to see if temp is climbing progressively or suddenly.
On packages with integrated refrigerated dryer, the SIGMA CONTROL 2 monitors dryer operation. Dryer fault triggers if the dryer controller generates an alarm. Check the dryer controller (separate display inside the package) for a specific fault. Common: dryer refrigerant pressure alarm, condenser fan fault, or high pressure dewpoint.
SIGMA CONTROL 2 tracks service intervals by operating hours. Service due alerts appear in advance of the actual service interval (configurable, typically 100 hours before). Perform Kaeser-specified maintenance and reset the service counter in the SIGMA CONTROL 2 menu (requires service password).
SIGMA CONTROL 2 supports Modbus, PROFIBUS, PROFINET, and Ethernet. A communication fault means the controller cannot communicate with the BMS, master controller, or SIGMA NETWORK. Check network cable connections and verify IP address configuration.
| Part | Notes |
|---|---|
| Oil separator element | Kaeser-specific - match model |
| Oil filter element | Match package model |
| Pressure transducer | Check signal output (typically 4-20 mA) |
| Temperature sensor | NTC thermistor - check resistance |
| Condensate drain solenoid | Match voltage and orifice size |
| Fan motor contactor | Check contact condition |
Before ordering, match the commercial equipment part to the package model, electrical rating, alarm text, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: Kaeser SIGMA CONTROL 2 can be connected to SIGMA NETWORK for remote monitoring. Kaeser service centers can remotely access fault logs and performance data. Register the compressor on SIGMA NETWORK to enable predictive maintenance alerts.
A dirty cooler, low oil condition, high ambient temperature, or cooling-air restriction usually causes this shutdown. Clean the coolers, check oil condition, and review the controller temperature trend before restarting.
Do not clear the service counter until the scheduled maintenance is complete. The controller tracks operating-hour intervals, and resetting early can hide oil filter, separator, and inspection work that protects the compressor.
Check the pressure transducer wiring, connector, supply voltage, and 4-20 mA signal before replacing the sensor. Match the replacement by pressure range, thread, and package model.