Kaeser SIGMA CONTROL 2 Fault Codes: Complete Guide

3 min read
⚡ Quick Answer

Kaeser SIGMA CONTROL 2 fault codes and diagnostics. Compressor warnings, shutdowns, causes, and technician-level troubleshooting.

Difficulty Pro recommended
Est. time 1-3 hrs

Kaeser SIGMA CONTROL 2 Fault Codes

Kaeser compressors with SIGMA CONTROL 2 (second generation) use text-based alarm messages displayed on the controller panel. The SIGMA CONTROL 2 provides more detail and connectivity than the original Sigma Control, including Ethernet integration and remote monitoring via SIGMA NETWORK.

SIGMA CONTROL 2 Fault Reference

Alarm MessageCategoryCommon CauseAction
Final compression temp — WarningWarningApproaching high temp limitClean coolers, check oil
Final compression temp — ShutdownShutdownExcessive temperatureClean coolers, check oil, check ambient
Motor protection — ShutdownShutdownMotor overloadCheck motor amps and load
Emergency stop — ActiveShutdownE-stop circuit openCheck all E-stop switches
Pressure sensor — FaultWarningFailed pressure transducerCheck sensor wiring and signal
Temperature sensor — FaultWarningFailed temperature sensorCheck sensor resistance
Dryer — FaultWarningIntegrated dryer alarmCheck refrigerant dryer operation
Service — RequiredMaintenanceService interval reachedPerform scheduled service
Fan motor — FaultShutdownCooling fan motor faultCheck fan motor amps and contactor
Condensate drain — FaultWarningDrain solenoid not operatingCheck drain solenoid and timer
Oil filter — ServiceMaintenanceOil filter replacement dueReplace oil filter element
Differential pressure — HighWarningSeparator element cloggedReplace separator element
Communication — FaultWarningNetwork communication lossCheck Ethernet and network config
Phase — FaultShutdownPhase loss or reversalCheck input power quality

Most Common SIGMA CONTROL 2 Faults

Final Compression Temp — Shutdown

Kaeser’s shutdown threshold is typically 110°C (230°F). Warning precedes shutdown by approximately 5°C. Root cause is almost always a dirty cooler. Kaeser SIGMA CONTROL 2 logs the temperature trend — review to see if temp is climbing progressively or suddenly.

Dryer Fault

On packages with integrated refrigerated dryer, the SIGMA CONTROL 2 monitors dryer operation. Dryer fault triggers if the dryer controller generates an alarm. Check the dryer controller (separate display inside the package) for a specific fault. Common: dryer refrigerant pressure alarm, condenser fan fault, or high pressure dewpoint.

Service Required

SIGMA CONTROL 2 tracks service intervals by operating hours. Service due alerts appear in advance of the actual service interval (configurable, typically 100 hours before). Perform Kaeser-specified maintenance and reset the service counter in the SIGMA CONTROL 2 menu (requires service password).

Communication Fault

SIGMA CONTROL 2 supports Modbus, PROFIBUS, PROFINET, and Ethernet. A communication fault means the controller cannot communicate with the BMS, master controller, or SIGMA NETWORK. Check network cable connections and verify IP address configuration.

Parts Commonly Needed

PartNotes
Oil separator elementAmazon | Kaeser-specific — match model
Oil filter elementAmazon | Match package model
Pressure transducerAmazon | Check signal output (typically 4–20 mA)
Temperature sensorAmazon | NTC thermistor — check resistance
Condensate drain solenoidAmazon | Match voltage and orifice size
Fan motor contactorAmazon | Check contact condition

Pro tip: Kaeser SIGMA CONTROL 2 can be connected to SIGMA NETWORK for remote monitoring. Kaeser service centers can remotely access fault logs and performance data. Register the compressor on SIGMA NETWORK to enable predictive maintenance alerts.