Sabroe oil pressure transmitter
Relevant for low oil differential alarms after oil level and pump operation are verified.
Sabroe compressor alarm guide for refrigeration trips, oil pressure, discharge temperature, suction pressure, ammonia safety checks, and sensors.
Sabroe compressor alarm guide for refrigeration trips, oil pressure, discharge temperature, suction pressure, ammonia safety checks, and sensors.
Parts to price first
Relevant for low oil differential alarms after oil level and pump operation are verified.
Use for ID 37 checks only after confirming suction pressure, oil cooling, and Vi control.
Common service item for oil filter differential pressure and oil system alarms.
Match range, refrigerant compatibility, thread, and connector before replacement.
Sabroe industrial refrigeration compressors use controller-based shutdown IDs, not generic motor fault lights. On SAB screw compressors and HPC reciprocating packages, the controller watches suction pressure, discharge pressure, discharge temperature, oil differential pressure, oil temperature, filter differential pressure, motor protection, and communication signals. When any monitored point crosses its shutdown threshold, the controller stops the compressor and logs an alarm or shutdown ID.
This guide covers the Sabroe SAB 128, SAB 163, SAB 202 screw compressor family, HPC reciprocating packages, and the controller environment you will see on UniSAB III or SABview-style HMIs.
Sabroe controllers separate alarms from shutdowns:
On UniSAB III screw compressor packages, the most important shutdown and alarm IDs are:
| ID | Alarm / Shutdown Text |
|---|---|
| 31 | Low suction pressure alarm + shutdown |
| 32 | High suction pressure alarm |
| 35 | Low discharge pressure shutdown |
| 36 | High discharge pressure alarm + shutdown |
| 37 | High discharge temperature alarm + shutdown |
| 38 | Low oil pressure (differential pressure) alarm + shutdown |
| 41 | Low oil temperature alarm + shutdown |
| 42 | High oil temperature alarm + shutdown |
| 43 | High oil filter differential pressure alarm + shutdown |
| 44 | Oil system error shutdown |
| 46 | Compressor motor overload shutdown |
| 47 | Compressor motor error / emergency stop / HP shutdown |
| 49 | High motor temperature shutdown |
| 57 | High differential pressure (Pc minus Pe) alarm + shutdown, HPC only |
| 69 | Low discharge gas superheat alarm + shutdown |
| 84 | Low lubricating pressure alarm + shutdown |
| 86 | High internal suction pressure alarm + shutdown |
| 87 | High pressure ratio alarm + shutdown |
| 91 | High separator flow alarm |
| 92 | Low main oil pressure alarm |
| 93 | Oil system error alarm or no evaporator flow shutdown |
| 94 | No condenser flow shutdown |
| 95 | High process in temperature alarm + shutdown |
| 96 | Low process in temperature alarm + shutdown |
| 97 | Emergency stop shutdown |
| 104 | Low-low oil pressure shutdown |
| 105 | Oil pump low pressure alarm + shutdown |
For HPC reciprocating compressors, the core IDs stay similar, but you also see high oil pressure, intermediate pressure, and high liquid level alarms.
Most SABview HMIs follow the same logic even if the graphics differ:
On UniSAB III, press F4 / RESET. The controller will only clear a shutdown if the trip condition has disappeared. If the root cause is still present, the controller keeps the shutdown active and flashes red again.
Meaning: The condensing side pressure rose above the alarm limit and then crossed the shutdown limit. On standard screw packages, the factory high discharge pressure setting is often 15 bar alarm and 16 bar shutdown for lower-pressure setups. On HPC high-pressure machines, the factory values run much higher, commonly 33 bar alarm and 35 bar shutdown.
Most common causes:
Diagnosis steps:
Fix: Restore condenser capacity first. Clean condenser surfaces, restore fan or pump operation, open closed valves, and purge non-condensables if the plant procedure allows it.
Meaning: Suction pressure dropped below the low alarm limit and then below the shutdown limit while the compressor was running.
Most common causes:
Diagnosis steps:
Fix: Restore evaporator load or liquid feed. If the compressor unloaded too slowly, reduce capacity manually after restart and watch suction stabilize.
Meaning: The discharge gas temperature crossed the high alarm and then high shutdown limit. On many SAB screw compressors, factory shutdown starts around 100°C. On HPC and other reciprocating high-pressure packages, the shutdown limit can run around 125°C and higher depending on design.
Most common causes:
Diagnosis steps:
Fix: Correct the load condition before chasing sensors. Restore suction pressure, fix oil cooling, and verify Vi control.
Meaning: The controller calculated low oil differential pressure. On Sabroe packages, the controller usually calculates oil differential as oil pressure after the filter minus suction pressure, with model-specific exceptions.
Factory references from UniSAB III:
Most common causes:
Diagnosis steps:
Fix: Do not keep resetting a low oil pressure trip. Verify oil level, oil pump operation, oil filter condition, and oil temperature before restart.
Meaning: Oil temperature fell below the safe minimum. Sabroe manuals call out 40°C as a common low shutdown threshold for many screw packages and 40°C as the minimum oil temperature before startup on SAB 202 units.
Most common causes:
Diagnosis steps:
Fix: Let the oil reach operating temperature before restart. Repair the heater circuit if the temperature never rises.
Meaning: Oil temperature climbed above the permitted limit. Sabroe commonly sets the high alarm near 60 to 75°C and shutdown near 65 to 80°C on screw compressors, depending on the model.
Most common causes:
Diagnosis steps:
Fix: Restore oil cooling and confirm the correct oil grade for the refrigerant and operating range.
Meaning: Pressure drop across the oil filter exceeded the alarm and shutdown limit. Sabroe manuals call for filter replacement once the pressure drop exceeds about 0.7 bar on SAB 202 operating guidance. UniSAB III factory alarm settings often run around 0.7 to 1.2 bar, depending on the compressor family.
Most common causes:
Diagnosis steps:
Fix: Replace the oil filter. If the new filter plugs quickly, stop and inspect bearings, oil condition, and internal wear sources.
Meaning: The motor overload protection opened.
Most common causes:
Diagnosis steps:
Fix: Do not simply reset the overload and restart. Confirm that motor current returned to normal and that process pressures make sense.
Meaning: The controller saw an external motor protection or emergency stop event. The same ID can appear for motor guard trips, emergency stop activation, or a hardwired high-pressure safety input.
Diagnosis steps:
Reset: Correct the field condition, then press F4 / RESET. If the machine is in remote or auto mode, it may restart on its own when you clear the shutdown. Make sure the system is ready before reset.
Meaning: The motor thermistor input tripped.
Most common causes:
Diagnosis steps:
Many newer Sabroe screw packages use the Sabroe Vibration Monitoring system. The package may show a dedicated vibration alarm in the package PLC or pass it to UniSAB as an external or user alarm.
Meaning: Bearing vibration exceeded the warning or shutdown threshold.
Most common causes:
Diagnosis steps:
Fix: Treat vibration trips as mechanical warnings. Do not run repeated restart cycles until you inspect bearings and alignment.
Sabroe controllers can also stop a machine for communication or control faults.
Most common causes:
Diagnosis steps:
Fix: Restore the communication link first. If the drive link returns and all permissives are healthy, clear the shutdown and confirm the controller sees valid drive feedback.
When a Sabroe compressor trips, check interlocks in this order:
That order saves time because oil pressure, emergency stop, and motor protection trips often block every other restart attempt.
| Part | Application | Notes |
|---|---|---|
| Oil filter element | SAB 128/163/202, HPC | Replace when differential pressure rises; investigate debris source if repeat plugging occurs |
| Oil separator level switch | Screw packages with oil system error alarm | Trips ID 44 or related oil system alarms |
| Pressure transmitter, Danfoss AKS 3000 | Suction, discharge, oil pressure | Sabroe commonly uses -1 to 9 bar, -1 to 25 bar, or -1 to 59 bar transmitters |
| Pt100 temperature sensor | Discharge temp, oil temp, process temp | Check resistance and wiring before replacing controller |
| Vibration sensor | Packages with Sabroe Vibration Monitoring | Trend bearings and coupling condition |
| Oil heater | Standstill oil temperature protection | Critical for avoiding low oil temperature trips |
| Oil pump | Screw and HPC packages with pumped oil system | Check set points and start timers in controller |
| Position transmitter | Capacity slide and Vi slide on SAB screw compressors | Bad feedback can cause capacity or Vi position faults |
Sabroe operating guidance for SAB 202 units calls for daily logging of:
Also check oil filter pressure drop. Sabroe guidance says to replace the filter as soon as the pressure drop exceeds 0.7 bar to avoid a forced shutdown.
| Symptom | First ID to check | Likely cause |
|---|---|---|
| Compressor trips on hot day | 36 | Condenser problem or non-condensables |
| Compressor trips after low load period | 31 or 37 | Starved evaporator, low suction |
| Trip after startup | 41 or 38 | Oil too cold or oil differential not established |
| Repeated oil alarms | 38, 43, 105 | Low oil level, blocked filter, weak pump |
| Motor trip with normal pressures | 46 or 49 | Electrical issue or motor cooling problem |
| Controller says drive link missing | 89, 90, 91 | VSD or communication fault |
| HPC unit trips on pressure spread | 57 | Pc minus Pe too high |
Before ordering, match the refrigeration part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If a Sabroe machine gives you multiple alarms at once, trust the first one in history, not the last one on screen. The last alarm often shows the consequence. The first alarm usually shows the cause.
Match the compressor package, controller alarm history, pressure range, thread type, and sensor signal before ordering. These focused searches line up with the oil, temperature, and pressure faults covered above:
Read live discharge pressure before reset, then check condenser fans, condenser water or spray flow, valve position, fouled condenser surfaces, and non-condensables.
Low oil differential can mean low oil level, pump failure, hot/thin oil, a restricted oil filter, transmitter drift, or refrigerant dilution. Restarting without fixing the cause can damage the compressor.
Record suction pressure, discharge pressure, oil differential pressure, oil temperature, discharge temperature, motor current, and alarm history so the reset does not erase the best troubleshooting evidence.