⚡ Quick Answer

Yaskawa GA800 E15 indicates a communication error on an installed option or control link. Learn how to diagnose and repair this fault.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa GA800 E15 Fault — What It Means

E15 on a Yaskawa GA800 is a communication-related fault tied to a specific option board or control link installed in the drive. The most common interpretation is a communications error detected on the SI-F/G interface or another parameterized communication path used to send run commands or frequency references. The exact fault text depends on which communication option is fitted in your drive, so identifying the installed option card or control interface is the first step in diagnosis.

This fault is not a general drive failure. It means the drive has lost contact with the option module, received corrupted data on the communication link, or detected a parameter mismatch between the drive and the control source. The fault will persist until you remove the cause and reset the drive.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Record the exact fault code and text displayed, then identify which communication option or interface is installed in the drive. Check the drive label, installation documentation, or parameter group to confirm the option type before proceeding.
  2. Power down the drive safely and lock out incoming power. Open the drive enclosure and visually inspect the communication option card, its seating in the drive slot, and all cable connectors for looseness, bent pins, corrosion, or visible damage.
  3. Verify all communication-related parameters in the drive against the installation wiring and controller settings. Consult your model’s parameter table and correct any mismatches in communication source, protocol selection, baud rate, or control mode settings.
  4. Check cable routing, shielding, and grounding of the communication link. Verify that communication cables are routed away from power wiring, shields are grounded at one end only or as specified for your protocol, and termination resistors are installed correctly at both ends of the network.
  5. Swap-test the communication cable or option board with a known-good spare if available. If the fault clears with the replacement part, the original cable or option card is defective.
  6. Reset the fault only after correcting the cause by pressing the RESET button on the keypad. Restore power and monitor the drive for several cycles to confirm the fault does not return.
  7. If the fault persists with verified wiring and correct parameters, replace the failed communication option card. If the fault follows the drive after option replacement, the main control board is likely faulty and should be replaced.

Parts Often Needed

PartNotes
Yaskawa GA800 communication option cardAmazon | Match the exact option type (SI-F, SI-G, Modbus, EtherNet/IP, etc.) installed in your drive and verify compatibility with your drive model.
Communication cable and connector assemblyAmazon | Use manufacturer-specified cable type and length for your protocol. Verify shielding and termination requirements before installation.
GA800 main control boardAmazon | Required only if the fault persists after option card and cable replacement. Obtain the correct board for your drive’s voltage and size rating.

When to Call a Pro

Call a qualified drive technician or Yaskawa service representative if the fault returns after you have verified all parameters, replaced the communication cable and option card, and confirmed correct wiring and grounding. Persistent communication faults that survive hardware replacement usually indicate a failure on the drive’s main control board or a system-level configuration error that requires specialized diagnostic tools. Also call for help if you are not trained to safely work inside energized industrial equipment or if your process cannot tolerate extended downtime for trial-and-error troubleshooting.