Trane Precedent RTUs (3-10 ton) use an LED on the unit control module (UCM) to flash fault codes. Count flashes between 3-second pauses. Units with the Integrated Comfort System display codes on a thermostat or controller.
| Code | Fault Description | Common Cause | Action |
|---|---|---|---|
| 2 | Supply air sensor fault | Failed SAT sensor or wiring | Check thermistor resistance |
| 3 | Outdoor air sensor fault | Failed OAT sensor | Replace sensor |
| 4 | Return air sensor fault | Failed RAT sensor | Check wiring to sensor |
| 5 | Compressor trip | Compressor protection open | Check HP/LP switches, contactor |
| 6 | Low charge/low pressure | Low refrigerant or TXV failure | Check subcooling, superheat |
| 7 | High discharge temp | Refrigerant short, failed condenser fan | Check condenser fan, refrigerant charge |
| 8 | Heating lockout | Gas heating fault | Check igniter, gas valve, flame sensor |
| 9 | Economizer fault | Failed actuator or sensor | Check economizer actuator and damper |
| 10 | Supply fan fault | Failed blower motor or VFD | Check motor amps, run capacitor |
| 12 | Ignition failure | No gas, weak spark | Check gas pressure and igniter |
| 13 | Limit switch lockout | Persistent overtemperature | Clear airflow restriction before reset |
| 14 | Flame rollout trip | Cracked heat exchanger or blocked flue | Inspect heat exchanger |
Check HP switch setting (R-410A = 590 psi, R-22 = 380 psi) and LP switch. Verify refrigerant charge with superheat and subcooling measurements before adding refrigerant.
Work through ignition sequence: verify 24 VAC to igniter, check spark gap (1/8”), clean flame sensor, and confirm gas pressure at manifold (3.5 in. w.c. natural gas).
Three consecutive limit trips lock out the unit. The cause is almost always restricted airflow. Replace the filter, verify all dampers are open, and check blower motor speed.
| Part | Notes |
|---|---|
| UCM control board | Match to unit model and refrigerant type |
| SAT/OAT/RAT sensors | Thermistor type - check resistance vs. temp chart |
| Flame sensor | Clean with emery cloth before condemning |
| Run capacitor | Check microF value with capacitor meter |
| Limit switch | Match opening temperature rating |
For Trane rooftop and packaged-unit faults, confirm unit power, economizer inputs, low-voltage safeties, pressure controls, condenser airflow, filters, and active board history before ordering replacement controls.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: Trane Precedent units require the correct UCM firmware for the refrigerant type (R-22 vs. R-410A). Swapping boards without matching firmware causes erratic fault codes.