Complete Mitsubishi Mr. Slim error code guide. Covers all P, E, and U-series fault codes for commercial Mr. Slim PUHZ, PEA, and PKAA series units.
Complete Mitsubishi Mr. Slim error code guide. Covers all P, E, and U-series fault codes for commercial Mr. Slim PUHZ, PEA, and PKAA series units.
Likely parts to price
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Price this first on furnace ignition faults after cleaning and safety checks.
Common furnace start failure part. Confirm connector and model compatibility.
Higher-cost part to price only after power, sensor, and wiring checks.
Mitsubishi Mr. Slim is the commercial line of Mitsubishi Electric ductless and ducted mini-split systems, covering PUHZ, PEA, PKAA, PCA, and similar series from 1 to 5 tons. Error codes are displayed on the wired remote controller (PAR-31, PAR-40, or similar) or via the outdoor unit LED diagnostic sequence.
| Code | Description | Common Cause |
|---|---|---|
| P1 | Indoor unit intake temperature sensor fault | Check sensor at return air |
| P2 | Indoor unit pipe temperature sensor fault | Check liquid pipe sensor |
| P4 | Drain sensor fault | Float switch or drain sensor wiring |
| P5 | Drain pump fault | Condensate pump failure or blockage |
| P6 | Freeze protection trip | Low refrigerant, low airflow |
| P8 | Pipe temperature fault | TXV issue, refrigerant flow problem |
| P9 | Indoor fan motor fault | Fan motor or PCB |
| PA | Four-way valve fault | Stuck or failed reversing valve |
| PJ | Capacity mismatch | Indoor/outdoor capacity incompatibility |
| Code | Description | Common Cause |
|---|---|---|
| E0 | Remote control signal fault | Remote wiring or signal issue |
| E1 | Indoor unit PCB fault | Replace indoor control board |
| E3 | Indoor unit fan motor fault | Motor winding or capacitor |
| E4 | Indoor unit serial communication | Wiring between indoor boards |
| E5 | Indoor unit AC current protection | Overcurrent — check wiring |
| E6 | Compressor overcurrent | Check compressor and supply voltage |
| E7 | Fan motor overcurrent | Fan motor drawing excess amps |
| E9 | Electronic expansion valve fault | EEV coil or position sensor |
| Code | Description | Common Cause |
|---|---|---|
| U1 | Reverse phase detection | Check 3-phase power phasing |
| U2 | Power module fault | Outdoor IPM (inverter module) fault |
| U3 | Charge failure (first run) | Incomplete refrigerant charge |
| U4 | Serial communication fault | Check indoor/outdoor wiring |
| U5 | Abnormal indoor unit combination | Address conflict, unit mismatch |
| U6 | Compressor motor fault | Check inverter drive module |
| U7 | Inverter PCB fault | Outdoor inverter board failure |
| U8 | Outdoor fan motor fault | Fan motor or outdoor PCB |
Most frequent fault in cooling season:
The most common Mr. Slim multi-zone fault:
| Part | Notes |
|---|---|
| Indoor pipe temperature sensor | Part varies by model — 10K or 5K thermistor |
| EEV coil | Model-specific — match wiring harness |
| Indoor PCB | Match part number from unit nameplate |
| Outdoor inverter PCB | High-value part — verify fault before replacing |
| Condensate pump | Fits PCA/PKAA ceiling cassette models |
| Fan capacitor | Indoor or outdoor — match µF |
Mini-split and VRF faults usually come from condensate drainage, thermistors, indoor-outdoor communication wiring, outdoor airflow, inverter protection, or control-board inputs. Match the code to the exact indoor and outdoor model, then check filters, drains, coils, wiring terminals, and sensor seating before replacing electronics.
DIY vs Pro: Cleaning filters, clearing drains, checking obvious loose connectors, and power-cycling once are reasonable first steps. Refrigerant work, inverter-board diagnostics, high-voltage testing, and sealed-system repairs need a qualified HVAC technician.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: Mitsubishi Mr. Slim units store the last 4 fault codes in the PCB memory. On the wired remote PAR-31, navigate to CHECK > SELF DIAGNOSIS to view the fault history.