Skip to content
Industrial Error Code Fixes
Go back

Mitsubishi PEX City Multi Error Codes

⚡ Quick Answer

Mitsubishi PEX City Multi indoor-unit guide for P1, P2, P4, P5, P6, P8, drain, thermistor, float-switch, and coil-freeze faults.

⚡ AT A GLANCEScroll down for full repair guide
What it meansMitsubishi PEX City Multi indoor-unit guide for P1, P2, P4, P5, P6, P8, drain, thermistor, float-switch, and coil-freeze faults.
Most likely causeMost hvac faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededRun capacitor
Repair intent

Need this fixed instead of diagnosed?

Mitsubishi PEX City Multi indoor-unit guide for P1, P2, P4, P5, P6, P8, drain, thermistor, float-switch, and coil-freeze faults.

Likely parts to price

Price the common parts before you book service.

Run capacitor

Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.

Flame sensor

Price this first on furnace ignition faults after cleaning and safety checks.

Igniter

Common furnace start failure part. Confirm connector and model compatibility.

Control board

Higher-cost part to price only after power, sensor, and wiring checks.

Mitsubishi PEX City Multi Error Codes (Indoor Unit)

Mitsubishi City Multi PEX series indoor units display fault codes via LED on the unit PCB or on the system controller (MA Remote, G-50A, or AE-200). Codes are two-digit numbers: the first digit indicates the fault category, the second identifies the specific component.

PEX Indoor Unit Fault Code Table

CodeFault DescriptionCommon CauseAction
P1Intake air temp sensor faultOpen or short in sensorCheck sensor resistance (10kohm at 77 degrees F)
P2Pipe (liquid) sensor faultSensor failureCheck refrigerant pipe sensor
P4Drain pump faultDrain pump failure or float switchCheck pump operation and float switch
P5Drain float switch openHigh condensate levelClear drain pan, check drain pump
P6Fan motor faultIndoor fan motor failureCheck motor amps and operation
P8Pipe temp protectionExcessively high or low pipe tempCheck refrigerant charge and flow
P9Indoor unit error (communication)Branch controller addressCheck BC controller addressing
E1Outdoor unit errorFault from outdoor unitCheck outdoor unit PCB
E6No communication with outdoorCommunication wiringCheck transmission wiring
E7Fan lockFan motor lockedCheck fan blade and motor

Most Common PEX Indoor Faults

P4/P5 - Drain Issues

Commercial fan coil units accumulate condensate during cooling. P4 (drain pump fault) means the pump is not running or running dry. P5 means the float switch has lifted - the pan is full. Clear the drain line, clean the condensate pan, and verify the pump lifts to discharge height.

P6 - Fan Motor Fault

Check that the fan blade turns freely. PEX units use multi-speed motors. Verify the correct speed tap is selected. Measure motor amp draw and check run capacitor where applicable.

E6 - No Communication

City Multi uses a 2-wire transmission network (M-NET). Check that all indoor units have unique addresses on the branch controller. Verify cable polarity and maximum network length limits.

P8 - Pipe Temperature Protection

If pipe temperature is too high or too low, the unit shuts down to protect the refrigerant system. On PEX branch controller systems, check EEV position at the branch controller and verify refrigerant distribution to this branch.

Parts Commonly Needed

PartNotes
Intake or pipe sensorMitsubishi-specific thermistors
Drain pumpMatch voltage and lift height
Indoor PCBMatch PEX model and revision
Fan motorMatch speed, HP, and frame
Float switchUniversal float switch fits most pans

Technician Tips

Mini-split and VRF faults usually come from condensate drainage, thermistors, indoor-outdoor communication wiring, outdoor airflow, inverter protection, or control-board inputs. Match the code to the exact indoor and outdoor model, then check filters, drains, coils, wiring terminals, and sensor seating before replacing electronics.

DIY vs Pro: Cleaning filters, clearing drains, checking obvious loose connectors, and power-cycling once are reasonable first steps. Refrigerant work, inverter-board diagnostics, high-voltage testing, and sealed-system repairs need a qualified HVAC technician.

Need Replacement Parts?

Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Pro tip: Mitsubishi City Multi systems allow all indoor unit faults to be read from the G-50A or AE-200 centralized controller. Use the controller’s “Monitor” screen to see all unit statuses simultaneously without checking each indoor unit individually.


Need a professional? Compare HVAC repair options before replacing parts.