Run capacitor
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Mitsubishi PEX City Multi indoor-unit guide for P1, P2, P4, P5, P6, P8, drain, thermistor, float-switch, and coil-freeze faults.
Mitsubishi PEX City Multi indoor-unit guide for P1, P2, P4, P5, P6, P8, drain, thermistor, float-switch, and coil-freeze faults.
Likely parts to price
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Price this first on furnace ignition faults after cleaning and safety checks.
Common furnace start failure part. Confirm connector and model compatibility.
Higher-cost part to price only after power, sensor, and wiring checks.
Mitsubishi City Multi PEX series indoor units display fault codes via LED on the unit PCB or on the system controller (MA Remote, G-50A, or AE-200). Codes are two-digit numbers: the first digit indicates the fault category, the second identifies the specific component.
| Code | Fault Description | Common Cause | Action |
|---|---|---|---|
| P1 | Intake air temp sensor fault | Open or short in sensor | Check sensor resistance (10kohm at 77 degrees F) |
| P2 | Pipe (liquid) sensor fault | Sensor failure | Check refrigerant pipe sensor |
| P4 | Drain pump fault | Drain pump failure or float switch | Check pump operation and float switch |
| P5 | Drain float switch open | High condensate level | Clear drain pan, check drain pump |
| P6 | Fan motor fault | Indoor fan motor failure | Check motor amps and operation |
| P8 | Pipe temp protection | Excessively high or low pipe temp | Check refrigerant charge and flow |
| P9 | Indoor unit error (communication) | Branch controller address | Check BC controller addressing |
| E1 | Outdoor unit error | Fault from outdoor unit | Check outdoor unit PCB |
| E6 | No communication with outdoor | Communication wiring | Check transmission wiring |
| E7 | Fan lock | Fan motor locked | Check fan blade and motor |
Commercial fan coil units accumulate condensate during cooling. P4 (drain pump fault) means the pump is not running or running dry. P5 means the float switch has lifted - the pan is full. Clear the drain line, clean the condensate pan, and verify the pump lifts to discharge height.
Check that the fan blade turns freely. PEX units use multi-speed motors. Verify the correct speed tap is selected. Measure motor amp draw and check run capacitor where applicable.
City Multi uses a 2-wire transmission network (M-NET). Check that all indoor units have unique addresses on the branch controller. Verify cable polarity and maximum network length limits.
If pipe temperature is too high or too low, the unit shuts down to protect the refrigerant system. On PEX branch controller systems, check EEV position at the branch controller and verify refrigerant distribution to this branch.
| Part | Notes |
|---|---|
| Intake or pipe sensor | Mitsubishi-specific thermistors |
| Drain pump | Match voltage and lift height |
| Indoor PCB | Match PEX model and revision |
| Fan motor | Match speed, HP, and frame |
| Float switch | Universal float switch fits most pans |
Mini-split and VRF faults usually come from condensate drainage, thermistors, indoor-outdoor communication wiring, outdoor airflow, inverter protection, or control-board inputs. Match the code to the exact indoor and outdoor model, then check filters, drains, coils, wiring terminals, and sensor seating before replacing electronics.
DIY vs Pro: Cleaning filters, clearing drains, checking obvious loose connectors, and power-cycling once are reasonable first steps. Refrigerant work, inverter-board diagnostics, high-voltage testing, and sealed-system repairs need a qualified HVAC technician.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Pro tip: Mitsubishi City Multi systems allow all indoor unit faults to be read from the G-50A or AE-200 centralized controller. Use the controller’s “Monitor” screen to see all unit statuses simultaneously without checking each indoor unit individually.