Mitsubishi FR-D700 cooling fan
Use for THT thermal trips after cleaning the cabinet and confirming the fan is weak or stopped.
Mitsubishi FR-D700 guide for OC1, OV3, THT, THM, GF, PE, UVT, cooling fan, braking, motor cable, and parameter faults.
Mitsubishi FR-D700 guide for OC1, OV3, THT, THM, GF, PE, UVT, cooling fan, braking, motor cable, and parameter faults.
Parts to price first
Use for THT thermal trips after cleaning the cabinet and confirming the fan is weak or stopped.
Match the drive frame and model when display or button damage prevents setup and fault review.
Match voltage, horsepower, current rating, and enclosure needs before replacing a failed inverter.
Use only when fast stopping creates OV3 faults and the application supports a properly sized resistor.
The Mitsubishi FR-D700 is a compact inverter drive used on conveyors, small pumps, and packaging equipment. It displays fault codes directly on the built-in keypad in short alphanumeric form. The FR-D700 is reliable, but it is often installed in tight cabinets where heat, poor wiring, and abrupt parameter changes create nuisance trips.
| Code | Meaning |
|---|---|
| OC1 | Overcurrent during acceleration |
| OC2 | Overcurrent during constant speed |
| OC3 | Overcurrent during deceleration |
| OV1 | Overvoltage during acceleration |
| OV2 | Overvoltage during run |
| OV3 | Overvoltage during deceleration |
| THT | Inverter overtemperature |
| THM | Motor thermal overload |
| UVT | Undervoltage |
| GF | Ground fault |
| OLT | Stall prevention / overload trip |
| CPU | Internal control fault |
| Part | Notes |
|---|---|
| Cooling fan | Common thermal trip cause |
| Keypad | For damaged display/buttons |
| Replacement FR-D700 drive | For CPU faults |
| Braking resistor | If fast stop is application-critical |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Persistent CPU faults or repeated GF trips with the motor disconnected usually mean internal inverter damage. Mitsubishi drive service or a qualified controls technician should evaluate before the drive is put back into production.
OC1 means overcurrent during acceleration. Check the motor load, motor cable, acceleration time, and torque boost settings before replacing the drive.
THT is an inverter overtemperature fault. Clean the cabinet, check ambient temperature, and verify the cooling fan runs before condemning the VFD.
Replace the drive only after confirming input power, motor insulation, braking resistor sizing, fan operation, and parameters. CPU faults or repeated trips with the motor disconnected need a controls technician.