Goodman GMS96 furnace error codes: all flash codes for the popular 96% AFUE single-stage furnace with causes and fixes.
Goodman GMS96 furnace error codes: all flash codes for the popular 96% AFUE single-stage furnace with causes and fixes.
Parts to price first
Part: B1401015S / B1401015
Igniter part numbers named for ignition lockout faults.
Part: PCBBF118S / PCBBF133
Condensate trap references for pressure switch faults.
Part: B1370169 / B1370138
0.60 inch WC pressure switch references from the article.
Part: 20285401
Flame sensor listed in the parts table.
Capacitor size family named for slow blower and limit trips.
The Goodman GMS96 is a single-stage, 96% AFUE gas furnace and one of the most widely installed value-segment furnaces in North America. It uses a standard Goodman/Amana IFC control board with a diagnostic LED visible through the lower access panel. Like all 96% AFUE models, the GMS96 uses a secondary heat exchanger and condensate drain — making drain-related pressure switch faults the most common service issue.
| Flashes | Meaning | Most Common Cause |
|---|---|---|
| 1 | Lockout — retries exceeded | Ignition failure |
| 2 | Pressure switch stuck open | Condensate trap, hose, or inducer |
| 3 | Pressure switch stuck closed | Hose routing or switch failure |
| 4 | High limit device open | Dirty filter or blocked airflow |
| 5 | Flame without call / roll-out | Gas valve or safety switch |
| 6 | Reversed line polarity | Fix wiring at disconnect |
| 7 | Gas valve energized — no call | Board or gas valve fault |
| 8 | Low flame sensor signal | Clean flame sensor rod |
| 9 | Igniter fault | Check igniter continuity |
The GMS96 uses a plastic condensate trap assembly (Goodman part PCBBF118S and related variants). This trap is press-fit together and can develop hairline cracks at the joints over time, causing air leaks. Cracks may not be visible — submerse the trap in water while applying air pressure to check for bubbles.
The GMS96 pressure switch is typically rated at –0.60” WC. Check whether the inducer creates sufficient draft by temporarily connecting a manometer to the pressure switch port — draft should reach –0.60” or more during inducer operation.
The GMS96 uses a low-static airflow design. It’s sensitive to filter restriction. Goodman recommends checking the filter monthly during heating season. The GMS96 also uses a PSC blower motor — the 7.5 µF or 10 µF run capacitor is the first thing to check when the blower seems slow. A capacitor that reads below rated value (>10% low) means the motor isn’t reaching full speed, which causes limit trips.
The GMS96 uses a silicon nitride hot-surface igniter (Goodman B1401015S or B1401015). Typical life is 5–7 years. If the unit is older, the igniter is the first thing to replace during a lockout diagnosis. Cold resistance should measure 40–90 ohms; a reading of OL means the element is cracked and open.
For 2-flash / pressure switch:
For 1-flash / lockout:
| Part | Notes |
|---|---|
| Hot-surface igniter | Goodman B1401015S |
| Condensate trap | Goodman PCBBF118S or PCBBF133 |
| Pressure switch | 0.60” WC — Goodman B1370169 or B1370138 |
| Flame sensor | Goodman 20285401 |
| Blower run capacitor | 7.5 or 10 µF / 370V |
Goodman furnaces use a simple LED flash system on the control board. The diagnostic LED is usually visible through the blower compartment window. Count the flashes between pauses — that’s your error code. One flash = normal operation. Two flashes = pressure switch fault. Three flashes = limit switch. Four flashes = flame sensor. Goodman flame sensors are notorious for carbon buildup — cleaning with emery cloth every 2-3 years prevents most lockout calls. The control board on GMS8 and GMSS9 models is particularly sensitive to voltage fluctuations — if you see multiple different codes, check the transformer output (should be 24VAC ±10%).
Prevention: Install a whole-house surge protector on the furnace circuit to prevent board damage from power spikes.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If you’re seeing 7-flash or 5-flash codes (gas valve faults), or if the furnace has rolled out, stop using the furnace and contact a licensed HVAC technician before restarting.