FHP 10K temperature sensor
Part: 02531-016
Use for F1, F2, F3, or F4 only after the sensor wiring and resistance curve fail testing.
Florida Heat Pump fault-code guide for FHP geothermal units, water-loop trips, freeze protection, low pressure, high pressure, sensors, and resets.
Florida Heat Pump fault-code guide for FHP geothermal units, water-loop trips, freeze protection, low pressure, high pressure, sensors, and resets.
Parts to price first
Part: 02531-016
Use for F1, F2, F3, or F4 only after the sensor wiring and resistance curve fail testing.
Match refrigerant, pressure rating, terminals, and unit model before replacing E1 or E2 switches.
Price a TXV only after airflow, loop flow, charge, and temperature measurements support a restriction.
Match the full model and board number before replacing DDC electronics for communication or board faults.
Check the drain, pan, and pump first when E9 points to condensate overflow.
Florida Heat Pump (FHP), now part of Bosch Thermotechnology, manufactures water-source and geothermal heat pumps used in commercial and residential applications. FHP units display fault codes on the DDC (digital display controller) or communicate via the optional ECA (extended control accessory) board.
| Code | Description | Common Cause |
|---|---|---|
| E1 | High-pressure lockout | High loop/water temp, low airflow, dirty coil |
| E2 | Low-pressure lockout | Low refrigerant, low airflow, low loop flow |
| E3 | Freeze protection — refrigerant | Low refrigerant temp — airside issue |
| E4 | Freeze protection — water coil | Low entering water temperature |
| E5 | High discharge temperature | Low refrigerant, restricted TXV |
| E6 | Compressor overload | High amps — check compressor and supply voltage |
| E7 | Low voltage lockout | Supply voltage below minimum |
| E8 | Communication fault | Check wiring between control boards |
| E9 | Condensate overflow | Clogged drain pan or condensate pump |
| F1 | Entering water sensor fault | Check sensor wiring and resistance |
| F2 | Leaving water sensor fault | Check sensor at water outlet |
| F3 | Entering air sensor fault | Check sensor at return air |
| F4 | Leaving air sensor fault | Check sensor at supply air |
| H1 | Hard lockout | 3 fault trips — manual reset required |
The most common FHP commercial fault, especially in summer:
FHP temperature sensors are typically 10K ohm NTC thermistors. Check:
FHP units manufactured after 2015 may show Bosch Thermotechnology branding. The fault codes and diagnostic procedures are identical. Service manuals reference both FHP and Bosch part numbers.
| Part | Notes |
|---|---|
| High/low pressure switch | Match refrigerant and trip pressure |
| Temperature sensor | 10K NTC thermistor — FHP part 02531-016 |
| TXV assembly | Match capacity and refrigerant type |
| DDC control board | FHP/Bosch part — match model number |
| ECA accessory board | For advanced controls and monitoring |
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Note: FHP/Bosch geothermal units have a hard lockout after 3 consecutive fault trips. After correcting the root cause, reset via the DDC controller or by cycling power at the breaker for 60 seconds.
E1 is a high-pressure lockout. Check entering water temperature, loop or cooling-tower flow, air filter, blower operation, coil condition, and refrigerant charge before replacing a switch.
E2 is a low-pressure lockout. Common causes include low refrigerant, restricted airflow, low loop flow, or a TXV restriction.
Correct the cause first, then reset from the DDC controller or cycle power at the breaker for about 60 seconds. If the same fault returns, diagnose the named circuit instead of repeating resets.