Danfoss RX controller guide for sensor, compressor, defrost, communication, relay, and refrigeration control fault diagnostics.
Danfoss RX controller guide for sensor, compressor, defrost, communication, relay, and refrigeration control fault diagnostics.
Likely parts to price
Common temperature-sensing fault part. Confirm resistance range and connector.
Useful to price for airflow, warm cabinet, or coil-icing symptoms.
Check this on ice buildup and defrost-cycle failures.
Low-risk maintenance item for water-flow and ice-quality complaints.
Danfoss refrigeration controllers use short alarm codes for sensor, temperature, defrost, and communication problems. The exact code list varies by controller family, but these are the alarms technicians see most often on RX-style walk-in and case controls.
| Code | Meaning | Quick Fix |
|---|---|---|
| E1 | Room sensor fault | Check room probe and wiring |
| E2 | Evaporator sensor fault | Check coil probe location and resistance |
| HA | High temperature alarm | Check box temp, airflow, and refrigerant system |
| LA | Low temperature alarm | Check setpoint and sensor calibration |
| dEF | Defrost fault / defrost overdue | Check heaters, termination probe, and timer settings |
| DO | Door open alarm | Check door switch and wiring |
| Com | Communication fault | Check network cable and addressing |
The controller cannot read the box temperature sensor. Check the probe resistance against the Danfoss temperature chart. A damaged probe wire near the door frame is common in walk-ins.
The coil sensor controls defrost termination and fan restart. If the probe is loose, hanging in free air, or failed, the controller may over-defrost or short-cycle defrost.
If the controller does not see the coil warm up during defrost, it alarms on defrost. Check electric heater continuity, hot gas solenoid operation, and the termination sensor.
| Part | Notes |
|---|---|
| Room probe | Replace on E1 alarms |
| Evaporator probe | Replace on E2 or defrost alarms |
| Defrost heater | Replace if open on ohm check |
| Door switch | Replace on repeated DO alarms |
Before ordering, match the refrigeration part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If the controller alarms after sensor replacement, the real problem may be refrigerant flow, hot gas piping, or a failed solenoid. A refrigeration technician should check the full system.