Carrier pressure switch
Part: HK06WC085 / HK06WC064
Pressure switch numbers listed in the parts table for code 31 diagnosis.
Carrier 31 pressure-switch guide for inducer draft, hoses, condensate traps, vent blockages, manometer checks, and part decisions.
Carrier 31 pressure-switch guide for inducer draft, hoses, condensate traps, vent blockages, manometer checks, and part decisions.
Parts to price first
Part: HK06WC085 / HK06WC064
Pressure switch numbers listed in the parts table for code 31 diagnosis.
Part: HC21ZE120A
OEM inducer assembly number listed for weak draft or failed inducer cases.
Part: HH18ZA641
Common Carrier furnace service part noted in the technician tips.
Part: HH18HA600 / HH18HA719
Switch numbers cited for Carrier furnace fault diagnosis; verify by model plate.
What it means: Code 3-1 indicates the pressure switch didn’t close (or opened unexpectedly) during the inducer pre-purge phase. The pressure switch is a safety device that confirms the draft inducer motor is running and creating sufficient negative pressure to safely remove combustion gases. If the switch doesn’t see adequate draft, the control board won’t open the gas valve — and the furnace shuts down with code 31.
Verify the draft inducer starts during the heat call. Initiate a heat cycle and listen for the inducer motor (the smaller motor on top/side of the heat exchanger) to start and ramp up within 5–10 seconds. If it doesn’t start, the problem is upstream of the pressure switch — check inducer motor wiring and control board output.
Inspect the pressure switch hose. With the furnace OFF, locate the small rubber hose running from the inducer housing port to the pressure switch (usually 1/4” to 3/8” diameter, 3–12 inches long). Disconnect both ends. Look for cracks, kinks, water inside the hose, or debris in either port. Blow through it to confirm it’s clear. Replace with matching ID/OD tubing if blocked or cracked — it’s less than $2 of material.
Check for water in the pressure switch. Disconnect the hose at the pressure switch inlet and tip the switch port down. If water drips out, condensate has been accumulating in the switch. Shake it dry (or replace), then fix the root cause — check the condensate drain line for blockage (blow it clear or pour water through it).
Test the pressure switch directly. With the furnace off, use a multimeter on continuity mode across the switch terminals. An open-style pressure switch (normally open) should show NO continuity at rest and continuity when you apply suction to the inlet port (use your mouth to apply gentle suction while watching the meter). If it won’t close under suction, the diaphragm is dead — replace the switch.
Measure the actual draft pressure. With a magnehelic gauge or manometer, tap into the inducer housing and measure draft pressure while the inducer runs. Compare to the switch rating (printed on the switch — typically -0.50” to -1.70” W.C. depending on the model). If draft is low but the inducer runs, check the flue for blockage and the inducer impeller for debris.
Inspect the flue pipe end cap and termination. Go outside and look at the PVC vent termination. Spiders, wasp nests, and ice buildup in winter are documented causes of flue obstruction that trigger pressure switch faults.
Clear and retest. After repair, restore power and run 3 complete heat cycles. Confirm code 31 does not return. If it returns intermittently (only when cold, only in rain), the problem is likely moisture/condensate-related and requires fixing the drainage system.
| Part | Where to Buy | Typical Cost |
|---|---|---|
| Pressure switch (Carrier #HK06WC085 or HK06WC064) | Carrier dealer, Johnstone Supply | $20–$50 |
| Draft inducer assembly (Carrier #HC21ZE120A) | RepairClinic, Carrier OEM | $120–$280 |
| Condensate drain line kit | Home Depot, HVAC Supply | $10–$25 |
| Pressure switch hose (3/8” ID vinyl, sold by foot) | Any hardware store | $2–$5 |
Carrier uses different diagnostic systems across furnaces, heat pumps, chillers, mini-splits, VRF equipment, rooftop units, and communicating controls. Confirm the full model number and whether the fault came from the indoor board, outdoor board, thermostat, or equipment controller before matching it to a repair path.
Start with power, wiring, airflow or water-flow, sensor, condensate, and safety-circuit checks before ordering control boards. If the same code returns after one reset and the basic cause is not obvious, test the named circuit instead of repeatedly cycling the equipment.
Common replacement parts for Carrier systems:
Before ordering, match the furnace part to the model number, electrical rating, and failure symptom. Check Carrier 31 pressure switch, inducer, hose, and manometer options on Amazon - prices and availability change frequently.
If you’ve cleared the hose, dried the switch, confirmed the inducer runs strongly, and the switch still won’t close — you need a tech with a manometer to measure actual draft. A furnace that produces too little draft for its pressure switch rating usually means either the inducer is failing internally (impeller wear) or there’s a major flue restriction. Both require hands-on diagnosis. Tell your tech: “Code 31, pressure switch won’t close. I’ve already cleared the hose and the switch tests good at rest. I need you to measure draft on the inducer.”
Pro tip: On 90%+ efficiency Carrier furnaces, always check the condensate drain trap for blockage before replacing the pressure switch. A blocked trap creates a positive pressure inside the inducer housing that can hold the pressure switch open even when everything else is working perfectly. It’s a 5-minute fix that saves a $40 part.
Code 31 means the pressure switch did not close, or opened unexpectedly, during the inducer pre-purge. The furnace stops because it cannot prove safe draft.
Check the pressure-switch hose, inducer port, condensate trap, vent termination, draft inducer operation, and actual draft pressure before replacing the switch.
Yes. On high-efficiency Carrier furnaces, condensate backing into the inducer or pressure-switch tubing can keep the switch open even when the switch itself is still good.