Insulation resistance tester
Use for phase-to-ground and phase-to-phase motor/cable checks before blaming the ACS580.
ABB ACS580 fault 2310 guide for overcurrent trips, motor cable shorts, megger checks, jammed loads, ramp settings, and safe reset decisions.
ABB ACS580 fault 2310 guide for overcurrent trips, motor cable shorts, megger checks, jammed loads, ramp settings, and safe reset decisions.
Parts to price first
Use for phase-to-ground and phase-to-phase motor/cable checks before blaming the ACS580.
Use when oil, flexing, crushed cable tray sections, or failed insulation point to the motor lead set.
Use for long motor leads or reflected-wave stress after cable and motor insulation tests pass.
Search by the exact ACS580 catalog number, voltage, current rating, enclosure, and option code only after external faults are ruled out.
ABB ACS580 fault 2310 is an output overcurrent trip. The drive measured current high enough to protect the inverter output stage, motor, and connected load.
Treat 2310 as a fault to diagnose before ordering parts. A bad motor cable, weak motor insulation, wrong motor data, or a locked pump or fan can destroy a replacement drive if you install hardware before isolating the cause.
| When 2310 appears | Most likely focus |
|---|---|
| Immediately on enable | Output short, connected contactor issue, hardware |
| During acceleration | Ramp too short, motor data, locked load |
| At constant speed | Mechanical load spike, cable fault, loose output |
| During deceleration | Load instability, control tuning, regen context |
| With motor disconnected | Drive output stage or current-sensing fault |
Use parts searches after the first electrical checks point to a component. For most 2310 trips, the right order is motor/cable test, load inspection, motor-parameter review, ramp adjustment, then ACS580 hardware evaluation.
If you need a replacement drive, match the complete ACS580 catalog number, voltage, current rating, enclosure rating, brake option, EMC option, and communication adapter before ordering.
Fault 2310 means output overcurrent. The ACS580 measured current above its trip limit, often from a shorted motor cable, weak motor insulation, a jammed load, wrong motor data, or acceleration that is too aggressive for the load.
Reset the ACS580 only after you record the fault logger data and check the motor cable, mechanical load, and motor parameters. Repeated resets after 2310 can damage the drive if a short or locked load remains.
Use the fault logger to see whether 2310 occurred during acceleration, steady speed, deceleration, or startup. Then isolate the motor and cable, test insulation resistance, verify motor nameplate data, and inspect the driven machine for binding.