Wilo pump float switch
Match cable length, switch type, and switching level for E062 or E090 drainage faults.
Wilo pump fault guide for Stratos MAXO, Stratos GIGA, TOP-S, Yonos MAXO, and CronoLine units: E-codes, sensors, wiring, BMS, and reset checks.
Wilo pump fault guide for Stratos MAXO, Stratos GIGA, TOP-S, Yonos MAXO, and CronoLine units: E-codes, sensors, wiring, BMS, and reset checks.
Parts to price first
Match cable length, switch type, and switching level for E062 or E090 drainage faults.
Match the pump model, connection size, and shaft seal type before ordering.
Match Stratos MAXO or Stratos GIGA module compatibility before wiring BMS communications.
Match microfarad value and voltage from the TOP-S single-phase pump nameplate.
Wilo is a German pump manufacturer with a large presence in HVAC, building services, and industrial circulation applications. Their smart pump lines — particularly the Stratos MAXO and Yonos MAXO — are standard equipment in commercial heating and cooling systems across Europe, North America, and globally.
When a Wilo pump faults, it displays an E-code (error) or W-code (warning) on the integrated display. Errors stop the pump; warnings allow the pump to continue but flag a condition that requires attention. This guide covers the Stratos MAXO, Stratos GIGA, TOP-S, Yonos MAXO, and CronoLine series, with full fault code tables, diagnosis procedures, and BMS/building automation interface notes.
Stratos MAXO — High-efficiency ECM motor, integrated display with full text and e-code readout, Modbus/BACnet/LON capable. Used in HVAC hydronic systems. Replaces Stratos series. Available 25–100 mm connections.
Stratos GIGA — Inline, high-flow commercial and industrial hydronic applications. Similar control interface to Stratos MAXO.
Yonos MAXO — Compact high-efficiency pump for residential and light commercial hydronic heating. Simplified display (LED indicator) compared to Stratos MAXO.
TOP-S — Standard inline circulation pump for heating and cooling. Basic 3-speed selection, no integrated display or e-codes — faults are symptom-based (won’t run, low flow, noise).
CronoLine — High-efficiency inline pump for HVAC. Configurable via display.
Note on code numbering: Wilo’s error code numbering varies somewhat between the pump-specific series (Stratos MAXO uses E4xx codes prominently) and the associated controller or building automation module (which uses E0xx, E1xx codes). The codes listed below are organized by series where relevant.
| Code | Fault | Series | Auto-Reset? |
|---|---|---|---|
| E401 | Unstable power supply | Stratos MAXO | No — manual |
| E404 | Motor / electronics fault | Stratos MAXO | No — manual |
| E006 | Rotating field error (phase sequence) | Stratos GIGA, CronoLine | Auto if corrected |
| E014.x | Leakage / moisture detected | Any with moisture probe | Manual |
| E040 | Level sensor fault | Systems with level sensor input | Auto if sensor reconnects |
| E062 | Dry running protection / min. water level | Waste water / flood systems | Manual** |
| E066 | High water alarm | Waste water / flood systems | Manual |
| E068 | External OFF contact active | Any with external control input | Auto when contact clears |
| E080.x | Pump fault (overload/contactor/motor) | Multi-pump controllers | Manual** |
| E085.x | Pump running time monitoring exceeded (old firmware) | Multi-pump controllers | Manual*** |
| E090 | Float switch plausibility error | Waste water systems | Check and reset |
| E140.x | Maximum pump starts exceeded | Multi-pump controllers | Manual*** |
| E141.x | Pump running time exceeded (new firmware) | Multi-pump controllers | Manual*** |
| W572 | System pressure warning | Stratos MAXO | Auto (warning only) |
What it means: The pump’s internal power monitoring detected voltage instability — typically a voltage sag, spike, or momentary dropout on the supply.
Causes:
Fix steps:
What it means: The pump’s internal electronics detected a fault in the motor drive circuit or ECM motor — this is the Stratos MAXO’s primary hardware fault code.
Causes:
Fix steps:
Reset: After clearing the mechanical cause, power cycle the pump (off 10 seconds, on). If E404 returns within seconds of restart without any mechanical binding, the drive board has failed.
What it means: The pump detected incorrect phase rotation (clockwise vs. counterclockwise) or is being operated on single-phase power when three-phase input is required.
Applies to: Stratos GIGA, CronoLine, and other three-phase Wilo pumps.
Fix steps:
What it means: The moisture/leakage probe installed in the motor housing or adjacent to the pump detected water intrusion.
Fix steps:
What it means: The external level sensor connected to the pump controller has lost signal — open circuit or sensor failure.
Fix steps:
What it means: The dry-running protection tripped. On drainage/waste water pumps, this means the water level dropped below the minimum before the pump was switched off. On fill systems, it means the minimum level was not reached.
Causes:
Fix steps:
What it means: Water level exceeded the high-water setpoint. On drainage/waste water systems, this is a critical alarm indicating the pump(s) are not keeping up with inflow.
Fix steps:
What it means: A digital input configured as “External OFF” has been activated — an external device (BMS, safety system, PLC) has commanded the pump to stop.
Fix steps:
What it means: The pump controller detected a pump-side fault. Depending on firmware version, this can mean:
Fix steps:
What it means: The pump ran continuously for longer than the configured maximum running time. This is a monitoring function to detect system conditions where a pump runs non-stop when it should cycle (e.g., a sump pump running for 4 hours straight may indicate a water ingress problem).
Fix steps:
What it means: The float switches are in an impossible sequence — for example, the high-water float is indicating “wet” while the low-water float is indicating “dry.” This cannot be physically correct and indicates wiring error or float failure.
Fix steps:
What it means: The pump has exceeded the configured maximum number of starts per hour. This protects the motor from overheating due to frequent starting (each motor start generates heat from inrush current).
Causes:
Fix steps:
What it means: W572 is a warning (not an error) on the Stratos MAXO indicating a system pressure condition — typically that the pump is detecting unusually low or high differential pressure that falls outside expected parameters. The pump continues to run.
Fix steps:
TOP-S and basic Wilo circulation pumps do not have display screens or error codes. Diagnosis is symptom-based:
| Symptom | Possible Cause | Fix |
|---|---|---|
| Pump connected but does not run; green LED off | Fuse blown; ground fault interrupter tripped; electrical fault | Check/replace fuse. Reset GFCI. Call service if fuse blows repeatedly |
| Pump connected but does not run; green LED on | Undervoltage; winding damage; failed capacitor (single-phase) | Check voltage at terminals. Replace capacitor (1-phase pumps only). Call service for winding fault |
| Pump runs but output too low; green LED on | Foreign body in impeller; wrong rotation direction; shut-off valve not fully open | Disassemble pump head and remove debris. Swap two phases (3-phase) to reverse rotation. Open valves fully |
| Pump noisy; green LED on | Air in pump; cavitation (insufficient suction pressure); foreign body; wrong rotation | Vent pump/system. Increase system feed pressure. Remove debris. Check rotation |
| Pump runs; motor overheating | Pump blocked; ambient too high; motor overloaded | Check impeller for debris. Verify pump is not dead-headed (discharge valve must be open) |
Wilo Stratos MAXO and Stratos GIGA support multiple BMS protocols:
Modbus RTU (RS485):
BACnet MS/TP:
LON (LonWorks):
SSM / SBM Relay (potential-free contacts):
Setting access via display: On Stratos MAXO, press and hold the display button to enter the menu. Navigate using the +/− buttons. Menu 4.24 shows the software version. Fault history is accessible in the diagnostics menu. Most BMS configuration is under Menu 5 (inputs/outputs) and Menu 6 (communication).
Stratos MAXO: Most errors require a manual reset via the integrated display. Press and hold the button on the display until the error is acknowledged (typically 3 seconds). If the error condition is still present, the error will return immediately after reset.
Power cycle reset: Turn off the supply isolator, wait 30 seconds, restore power. This will clear any non-latched faults. Latched faults (E062, E080) require the cause to be resolved and a manual display reset.
E404 reset after unblocking rotor: Power cycle only — do not attempt to reset via display while rotor is blocked.
On Stratos MAXO:
For the fault signal assistant and detailed menu descriptions, visit: wilo.com and navigate to Support → Fault Signal Assistant.
| Component | Fits | Part Notes |
|---|---|---|
| Motor/pump unit (complete) | Stratos MAXO 25–65 | Stratos MAXO uses a wet-rotor motor integrated with the pump. When E404 indicates electronics failure, the motor/pump assembly is typically replaced as a unit. Order by connection size and max head (e.g., Stratos MAXO 25/0.5–8) |
| Control board / electronics | Stratos MAXO | Internal drive electronics. Wilo service part only — not available through standard distribution. Requires Wilo service center |
| Float switch | Waste water / drainage models | SPST or SPDT float switch, cable-mounted. Specify cable length and switching level height. Wilo or generic equivalent (e.g., Speroni, FS series) |
| Level sensor (submersible) | DrainLift / waste water | Hydrostatic pressure sensor or float switch depending on model. Specify 4–20 mA or switch output |
| RS485 / Modbus interface module | Stratos MAXO, Stratos GIGA | Wilo-IF-Module RS485. Plugs into communication slot on motor head |
| BACnet module | Stratos MAXO | Wilo-IF-Module BACnet MS/TP. Requires BACnet license activation |
| Moisture/leakage probe | Any model with E014 input | Two-wire resistive probe. Wilo accessory part. Used with optional protection relay |
| Shaft seal kit | TOP-S, CronoLine, Stratos GIGA | Model-specific mechanical seal. Specify pump model number and connection size. Common suppliers: Roten, Burgmann, AES |
| Capacitor | TOP-S single-phase models | CBB60 or MKP capacitor. Specify µF value and voltage from pump nameplate. Standard capacitor — available from electrical suppliers |
| Terminal box / cover | Any model | Wilo part. Required if original is damaged or missing — prevents water ingress to electrical connections |
Before ordering, match the commercial equipment part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Annual (minimum):
Every 2–3 years:
After any system work (pipe modifications, chemical dosing):
Find replacement parts for Wilo pumps on Amazon:
E401 means unstable power supply. Check voltage at the pump terminals under load, inspect terminal torque and upstream wiring, and look for voltage sag from nearby large loads.
E404 points to a motor or electronics fault, often from a blocked rotor, dry operation, or internal electronics failure. Check that the rotor turns freely and the system is full before replacing the pump.
Errors stop the pump and require correction before restart, while warnings allow the pump to keep running but flag a condition that should be investigated.