Siemens S7-300 and S7-400 PLC guide for STOP mode, SF/BF LEDs, hardware errors, OB calls, and diagnostic buffer entries in STEP 7 or TIA Portal.
Siemens S7-300 and S7-400 PLC guide for STOP mode, SF/BF LEDs, hardware errors, OB calls, and diagnostic buffer entries in STEP 7 or TIA Portal.
Likely parts to price
Common VFD, drive, UPS, and cabinet overheating failure point.
Useful to price when faults involve display, keypad, or operator-panel behavior.
Low-cost first check for power-stage and line-side faults.
Price this on drive overvoltage, braking, or deceleration faults.
Siemens S7-300 and S7-400 PLCs indicate faults through front-panel LEDs, the diagnostic buffer (accessible via STEP 7 or TIA Portal), and OB (Organization Block) calls in the user program. Understanding these layers is key to fast diagnosis.
| LED | State | Meaning |
|---|---|---|
| RUN | Green solid | CPU executing program |
| STOP | Yellow solid | CPU stopped (no fault) |
| STOP | Yellow blinking | CPU in STOP due to fault |
| SF | Red solid | System/group fault |
| BF | Red solid | Bus fault (PROFIBUS/DP) |
| DC5V | Green solid | 5V internal supply OK |
| FRCE | Yellow | Force mode active |
| MAINT | Yellow | Maintenance required |
SF + STOP blinking together = hardware or software fault — read the diagnostic buffer immediately.
The diagnostic buffer stores the last 100 events including all faults. Access via:
STEP 7 (Classic):
TIA Portal:
| Event Code | Description | Cause |
|---|---|---|
| 16#A502 | Startup complete | Normal — CPU went from STOP to RUN |
| 16#A503 | STOP mode entered | Manual STOP or fault |
| 16#253A | OB not loaded — CPU stops | Missing OB (e.g., OB82 or OB86 not present) |
| 16#2521 | I/O access error | Module missing or failed at accessed address |
| 16#2522 | I/O write error | Output module fault |
| 16#2526 | Timeout on I/O access | Module not responding |
| 16#A29F | Configuration error | Hardware config doesn’t match physical racks |
| 16#4500 | Rack failure | Module in rack not communicating |
| 16#4B00 | PROFIBUS DP station failure | Remote DP device went offline |
| 16#CAFE | CPU memory card error | Remove and reinstall memory card |
The S7 calls specific OBs when faults occur. If the OB is not loaded in the CPU, the CPU goes to STOP mode instead of handling the fault gracefully.
| OB | Trigger | Common Requirement |
|---|---|---|
| OB80 | Cycle time fault (watchdog) | Needed if cycle time can be exceeded |
| OB81 | Power supply fault | Needed for redundant power supply systems |
| OB82 | Diagnostic interrupt | Needed for intelligent I/O modules with diagnostics |
| OB83 | Insert/remove module | Needed for hot-plug capable systems |
| OB84 | CPU hardware fault | Rare, needed for fault-tolerant systems |
| OB85 | Program sequence fault | Load OB to prevent CPU stop on error |
| OB86 | Loss of rack / DP station | Most commonly missing — add empty OB86 |
| OB122 | I/O access error | Load to prevent stop on missing I/O |
Siemens SINAMICS and SINUMERIK alarms use a 5-digit numbering system. The first digit indicates the source: 2xxxx = drive, 3xxxx = NCK, 4xxxx = PLC. View the drive’s own fault code on the BOP-2 operator panel before referencing the CNC alarm — the drive sub-code is often more specific than the CNC alarm description. Alarm 25000 (drive fault) with a sub-code of 30001 means “motor encoder 1 faulty” — check the encoder cable before replacing the motor. Siemens drives with DRIVE-CLiQ communication require the optical cables to be properly terminated — a loose connector produces intermittent 25000 alarms that appear at random.
Prevention: Maintain spare DRIVE-CLiQ cables in your cabinet. They’re the most common failure point in Siemens servo systems.
Before ordering, match the replacement part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Fastest fix for “OB not loaded” stops: Create an empty OB with the required number and download it to the CPU.
The BF LED indicates a PROFIBUS bus fault. Common causes:
Diagnostic: Read the diagnostic buffer for event 16#4B00 — it includes the DP address of the failed station.
The CPU tried to read or write an I/O address that doesn’t exist or belongs to a failed module.
Fix:
Default cycle time on S7-300: 150 ms. S7-400: 6000 ms. If exceeded, OB80 is called. If OB80 is missing, CPU stops.
Fix:
S7-400H fault events include redundancy state changes:
16#673E — Master/standby switchover16#6733 — H system partially degradedThese are not always errors — some are expected during updates or hardware changes. Check if the switchover was planned.