Schneider PowerPact breakers with Micrologic trip units display fault trip codes on the LCD display or trip indicator LEDs. The Micrologic 5.x, 6.x, and 7.x trip units provide detailed fault information.
| Fault / Trip Code | Meaning | Quick Fix |
|---|---|---|
| Ir — Long Time Overload | Sustained overcurrent | Reduce load or increase Ir setting |
| Isd — Short Time Delay | Short circuit detected | Check for fault on load side |
| Ii — Instantaneous Trip | Severe overcurrent or short circuit | Check for dead short on load |
| Ig — Ground Fault | Ground fault current detected | Locate ground fault with megohm meter |
| Zone — ZSI Trip | Zone-selective interlock trip | Check upstream/downstream ZSI wiring |
| U — Undervoltage | Voltage dropped below threshold | Check supply voltage and connections |
| OV — Overvoltage | Voltage exceeded threshold | Check supply voltage |
| THD — Harmonic Distortion | Harmonics above limit (Micrologic 7) | Check loads for harmonic sources |
The load current has exceeded the Long Time pickup (Ir) for longer than the time delay allows. This is the thermal-magnetic equivalent of a sustained overload. Check actual current with a clamp meter. If load is normal, verify the Ir setpoint is correctly configured for the load.
A high-magnitude overcurrent (but below instantaneous) caused a short-time delay trip. This is typical when a large motor starts across-the-line or when a fault develops over time. Check downstream equipment for incipient faults.
Micrologic 5.x and higher units have ground fault protection (LSIG). A ground fault trip requires finding and clearing the ground fault before resetting. Use a megohm meter on the load-side circuit with the breaker open and load disconnected.
The Micrologic trip unit stores the last trip cause in memory. Press the MEASURE button after the trip to view the trip cause, current level, and time on the LCD display.
| Part | Notes |
|---|---|
| Micrologic trip unit | Replaceable without replacing breaker |
| Auxiliary contact | Adds trip signal to SCADA |
| Shunt trip coil | Remote trip capability |
Before ordering, match the commercial equipment part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Persistent trips or damaged breaker mechanisms require a qualified electrician. Never defeat or bypass a protective trip device.