Schneider PowerPact Breaker Fault Codes

⚡ Quick Answer

Schneider PowerPact guide for Micrologic Ir, Isd, Ii, Ig, Zone, UV, OV, and THD trips on H, J, L, and M-frame breakers.

⚡ AT A GLANCEScroll down for full repair guide
What it meansSchneider PowerPact guide for Micrologic Ir, Isd, Ii, Ig, Zone, UV, OV, and THD trips on H, J, L, and M-frame breakers.
Most likely causeMost circuit-breaker faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededCooling fan
Repair intent

Need this fixed instead of diagnosed?

Schneider PowerPact guide for Micrologic Ir, Isd, Ii, Ig, Zone, UV, OV, and THD trips on H, J, L, and M-frame breakers.

Likely parts to price

Price the common parts before you book service.

Cooling fan

Common VFD, drive, UPS, and cabinet overheating failure point.

Control keypad

Useful to price when faults involve display, keypad, or operator-panel behavior.

Fuses

Low-cost first check for power-stage and line-side faults.

Braking resistor

Price this on drive overvoltage, braking, or deceleration faults.

Schneider PowerPact Fault Codes — Quick Reference

Schneider PowerPact breakers with Micrologic trip units display fault trip codes on the LCD display or trip indicator LEDs. The Micrologic 5.x, 6.x, and 7.x trip units provide detailed fault information.

Fault / Trip CodeMeaningQuick Fix
Ir — Long Time OverloadSustained overcurrentReduce load or increase Ir setting
Isd — Short Time DelayShort circuit detectedCheck for fault on load side
Ii — Instantaneous TripSevere overcurrent or short circuitCheck for dead short on load
Ig — Ground FaultGround fault current detectedLocate ground fault with megohm meter
Zone — ZSI TripZone-selective interlock tripCheck upstream/downstream ZSI wiring
U — UndervoltageVoltage dropped below thresholdCheck supply voltage and connections
OV — OvervoltageVoltage exceeded thresholdCheck supply voltage
THD — Harmonic DistortionHarmonics above limit (Micrologic 7)Check loads for harmonic sources

Most Common Trips

Ir Long Time Overload

The load current has exceeded the Long Time pickup (Ir) for longer than the time delay allows. This is the thermal-magnetic equivalent of a sustained overload. Check actual current with a clamp meter. If load is normal, verify the Ir setpoint is correctly configured for the load.

Isd Short Time Delay

A high-magnitude overcurrent (but below instantaneous) caused a short-time delay trip. This is typical when a large motor starts across-the-line or when a fault develops over time. Check downstream equipment for incipient faults.

Ig Ground Fault Trip

Micrologic 5.x and higher units have ground fault protection (LSIG). A ground fault trip requires finding and clearing the ground fault before resetting. Use a megohm meter on the load-side circuit with the breaker open and load disconnected.

Resetting After a Trip

  1. Turn the handle fully to OFF position — the breaker must click to OFF before it can be reset.
  2. Hold for 2 seconds.
  3. Turn to ON position.
  4. If the breaker trips immediately, do NOT retry — a fault is still present.

Micrologic Display Navigation

The Micrologic trip unit stores the last trip cause in memory. Press the MEASURE button after the trip to view the trip cause, current level, and time on the LCD display.

Parts Often Needed

PartNotes
Micrologic trip unitReplaceable without replacing breaker
Auxiliary contactAdds trip signal to SCADA
Shunt trip coilRemote trip capability

Need Replacement Parts?

Before ordering, match the commercial equipment part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Jump to Fix

When to Call a Pro

Persistent trips or damaged breaker mechanisms require a qualified electrician. Never defeat or bypass a protective trip device.