Skip to content
Industrial Error Code Fixes
Go back

Rheem Furnace 2 Flashes - Causes & Fix

3 min read
⚡ Quick Answer

Rheem 2-flash code means pressure switch stuck closed. Usually caused by failed switch, blocked tubing, or vent restriction.

Difficulty Pro recommended
Est. time 1-3 hrs

Rheem Furnace 2 Flashes — What It Means

On most Rheem furnaces, 2 flashes indicate the pressure switch is stuck closed or closed at a time it should be open. The control board sees the pressure-switch circuit in the wrong state before the inducer sequence begins, treating it as a pressure-switch fault. Always confirm the exact code definition on your furnace’s door-data label or installation manual, because Rheem control families vary by model.

This fault tells you the pressure switch is not behaving as the sequence expects. The switch should open when there is no call for heat and close only after the inducer creates proper draft. When it stays closed or fails to open, the furnace locks out to prevent unsafe operation.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Verify the exact code definition on the door-data label or installation manual for your specific Rheem model to confirm 2 flashes means pressure-switch fault.
  2. Check the pressure-switch tubing for cracks, kinks, water, blockage, or disconnection at both the switch nipple and the inducer tap.
  3. Inspect the inducer port and vent piping for obstructions, debris, or restrictions in the flue and fresh-air intake that would alter draft pressure.
  4. Clear the condensate drain and trap (on condensing furnaces) to make sure water backup is not affecting draft or switch operation.
  5. Test the pressure switch with the inducer off. With no call for heat, the switch contacts should be open. If they read closed on a meter, the switch has failed.
  6. Inspect wiring and connectors at the pressure switch and control board for looseness, corrosion, or damage that could create a false closed reading.
  7. Replace the pressure switch if it does not change state correctly during the draft sequence and all tubing, venting, and drain paths are clear.

Parts Often Needed

PartNotes
Pressure switchAmazon | Match the pressure setpoint stamped on the original switch or listed in your furnace manual.
Pressure-switch tubingAmazon | Use correct-diameter rubber or silicone tubing rated for furnace draft sensing.
Inducer motor assemblyAmazon | Required if draft is weak or the inducer does not spin properly during the call sequence.
Control boardAmazon | Order the board by your furnace model number if the circuit is falsely reported and all field components test good.

When to Call a Pro

Call a licensed HVAC technician if you are not comfortable working with gas appliances, 120V wiring, or draft-proving circuits. A technician has the meters and manometers to measure switch behavior, draft pressure, and circuit continuity accurately. If you have replaced the pressure switch and tubing but the fault persists, the problem may involve the inducer, venting design, control board, or an intermittent wiring issue that requires diagnostic tools and experience to isolate safely.

See Also


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
York Furnace 7 Flashes - Causes & Fix
Next Post
Trane Furnace 2 Flashes - Causes & Fix