Thermistor
Common temperature-sensing fault part. Confirm resistance range and connector.
Johnson Controls Penn fault guide for A421, A350, P70, pressure controls, temperature controls, sensor alarms, and reset checks.
Johnson Controls Penn fault guide for A421, A350, P70, pressure controls, temperature controls, sensor alarms, and reset checks.
Likely parts to price
Common temperature-sensing fault part. Confirm resistance range and connector.
Useful to price for airflow, warm cabinet, or coil-icing symptoms.
Check this on ice buildup and defrost-cycle failures.
Low-risk maintenance item for water-flow and ice-quality complaints.
Johnson Controls Penn controls show up in rooftop units, walk-ins, chillers, and process cooling equipment. Most Penn controls do not use long digital fault logs. They trip on pressure, temperature, or sensor input and the connected equipment locks out.
| Fault / Condition | Meaning | Quick Fix |
|---|---|---|
| Sensor Error | Temperature sensor open or shorted | Check sensor resistance and wiring |
| High Pressure Trip | Pressure exceeded cutout | Check condenser airflow and charge |
| Low Pressure Trip | Suction pressure too low | Check charge and evaporator flow |
| Control Output Not Energizing | Relay failed or no control power | Check 24VAC / line voltage and relay |
| Manual Reset Open | Safety control tripped and latched | Find root cause before reset |
| Display Blank | No power to control | Check transformer, fuse, and wiring |
Penn A421 and A350 digital controls use a thermistor sensor. If the sensor opens or shorts, the display shows an error and the relay output drops out. Check the sensor plug, then measure resistance. A typical 10K sensor reads about 10,000 ohms at 77°F.
Penn pressure controls are often wired in series with the compressor contactor coil. A high pressure trip means the control opened the circuit to protect the compressor. Check condenser fan operation, condenser coil cleanliness, and refrigerant overcharge.
A low pressure safety opens when suction pressure falls too low. Common causes are low refrigerant charge, iced evaporator coil, plugged TXV screen, or low airflow across the evaporator.
| Series | Type | Common Use |
|---|---|---|
| A421 | Digital temperature control | Walk-ins, condensers, pump control |
| A350 | Electronic temperature control | HVAC and refrigeration |
| P70 | Mechanical pressure control | Refrigeration safety |
| P78 | High/low pressure control | Compressor protection |
Before ordering, match the refrigeration part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
If a Penn safety control keeps opening, do not jumper it out and walk away. Find the system problem first. Refrigerant work needs an EPA-certified technician.