EVAPCO cooling towers and evaporative condensers with PMC (Packaged Mechanical Component) control panels or VFD systems generate fault conditions from motor protection, temperature monitoring, and water management systems.
| Fault | Meaning | Quick Fix |
|---|---|---|
| Fan Motor Fault | Motor overload or trip | Check motor amps, bearings, and connections |
| High Leaving Water Temp | Leaving water above setpoint | Check fan operation and load balance |
| Low Basin Level | Makeup water not keeping up | Check makeup valve and inlet pressure |
| High Basin Level | Overflow condition | Check float valve and drain |
| Vibration Alarm | Excessive vibration detected | Inspect fan, shaft, and bearings |
| Freeze Alarm | Basin approaching freeze temp | Check heater and circulation |
| VFD Fault | Drive fault on fan motor | Refer to VFD fault code |
| Motor Phase Fault | Phase loss or imbalance | Check supply fuses and connections |
EVAPCO towers use axial or centrifugal fans. Motor overloads are caused by: ice buildup on fan blades in winter, worn motor bearings increasing load, blade pitch set incorrectly, and belt slippage on belt-drive models. Check motor amperage and compare to nameplate. Inspect bearings for roughness or excessive play.
If the tower is not maintaining approach temperature, check: fan speed (VFD may be in low-speed or manual mode), drift eliminators and distribution basins for scale buildup, and whether the heat load has increased beyond the tower’s rated capacity.
Cold weather tower operation is critical. EVAPCO towers use basin heaters to prevent freeze-up. Check the heater element with an ohmmeter. Verify the freeze protection thermostat setpoint. EVAPCO recommends maintaining basin water temperature above 35°F.
EVAPCO LSTE closed-circuit evaporative coolers add additional monitoring:
| Interval | Task |
|---|---|
| Weekly | Check basin level and water quality |
| Monthly | Inspect fan operation and motor amps |
| Annually | Clean tube bundle (LSTE), inspect fill, check basin sealant |
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
EVAPCO service centers provide commissioning, inspection, and component replacement. Contact EVAPCO at 1-410-756-2600.