Eaton Digitrip RMS module
Match breaker frame, sensor rating, and trip-unit family before replacing electronics.
Eaton Magnum DS, PowerDefense, and Cutler-Hammer circuit breaker fault codes and trip indicators: causes and reset procedures.
Eaton Magnum DS, PowerDefense, and Cutler-Hammer circuit breaker fault codes and trip indicators: causes and reset procedures.
Parts to price first
Match breaker frame, sensor rating, and trip-unit family before replacing electronics.
Use for alarm or status contact failures after confirming the breaker mechanism is healthy.
Select only by exact breaker series and voltage rating.
Use during ground-fault and post-trip inspection before re-energizing equipment.
Eaton Magnum DS and PowerDefense (formerly Cutler-Hammer) air circuit breakers use the EATON/Digitrip RMS 810/910 and PowerNet trip units. Faults are shown on LED panels, trip cause indicators, and via PowerNet communication.
| Fault / Indicator | Meaning | Quick Fix |
|---|---|---|
| Trip - Long Time (LT) | Sustained overload | Reduce load, check current |
| Trip - Short Time (ST) | Short-circuit delay zone | Locate and clear fault |
| Trip - Instantaneous (INST) | High-level fault current | Inspect load and wiring immediately |
| Trip - Ground Fault (GF) | Earth fault (Digitrip 5/8/9) | Find ground fault source |
| Trip - Neutral Overcurrent | Neutral conductor overloaded | Check for harmonics |
| TEST - Trip | Manual trip test result | Normal - reset and close |
| Zone Selective Interlock | Downstream breaker tripped | Find tripped downstream breaker |
| PowerNet: Comm Fault | Network communication lost | Check wiring to PowerNet |
| Maintenance Indicator | Inspection interval reached | Schedule maintenance |
| ALARM - Overload | Pre-trip warning | Reduce load before trip |
Check actual load current on all three phases. On three-phase systems with high harmonic content (VFD loads, UPS systems), neutral currents can be very high - this can cause long-time trips even when phase currents look normal. Verify Digitrip settings match the conductor and equipment ratings.
Eaton Magnum breakers support ZSI - when a downstream breaker detects a fault, it signals upstream breakers to add a short-time delay, allowing the closest breaker to clear the fault selectively. If ZSI faults are appearing, check the ZSI wiring between breakers and verify ZSI is enabled in all breaker settings.
Eaton Digitrip 810/910 ground fault protection trips when ground fault current (measured via a core balance CT or summation of phase currents) exceeds the Ig setting. Check for leakage current paths in the load - especially motors with degraded winding insulation and cables exposed to moisture.
An instantaneous (INST) trip on Eaton breakers occurs at 2–10× rated current. This is nearly always a fault in the load circuit. Inspect the load terminals, cables, and equipment before attempting a reset.
| Part | Notes |
|---|---|
| Digitrip RMS module | Replace on electronics failure |
| Arc chutes | Inspect after fault trips |
| Auxiliary/alarm contacts | Replace when worn |
| PowerNet communication module | Replace on comm fault |
| Spring charging motor | Replace on slow charge or no-charge |
Before ordering, match the commercial equipment part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Magnum DS maintenance, contact inspection, and trip unit calibration require training. Never reset after an instantaneous trip without an electrician inspecting the load circuit.
A long-time trip means sustained overload. Measure actual load current on each phase and confirm the trip settings match the conductors and equipment.
Ground fault means current is leaking to ground through wiring, motor windings, or connected equipment. Locate and clear the fault before resetting.
No. An instantaneous trip usually means high fault current, so the load circuit should be inspected before the breaker is closed again.