Carrier 24VNA6 Greenspeed guide for Infinity faults 168, 178, 179, inverter trips, control-board errors, refrigerant faults, and sensor checks.
Carrier 24VNA6 Greenspeed guide for Infinity faults 168, 178, 179, inverter trips, control-board errors, refrigerant faults, and sensor checks.
Parts to price first
Part: HH79NZ074
Sensor number cited for 24VNA6 ambient and coil sensor faults.
Part: 24VNA6 control board
Board listed for EEV driver faults and control-board faults; verify exact model revision.
Part: Infinity Touch
Thermostat listed for full Infinity fault-code display on the 24VNA6.
Part: Carrier heat pump pressure switch
Pressure switch listed for persistent code 24 trips after airflow and charge checks.
Part: 24V solenoid coil
Solenoid coil listed for code 63 reversing-valve faults with confirmed 24V signal.
The Carrier Infinity 24VNA6 is the flagship residential heat pump in Carrier’s lineup, the Greenspeed Intelligence platform. It uses a variable-speed inverter-driven compressor capable of modulating from roughly 25% to 100% capacity, the Infinity communicating system bus, and full integration with the Infinity Touch thermostat. When something fails on the 24VNA6, the Infinity system reports detailed numeric fault codes directly on the thermostat display. This guide covers every code the system generates, what each means at the component level, and how to diagnose and fix it.
The 24VNA6 communicates entirely through the Infinity system bus, a 4-wire communicating network connecting the outdoor unit, air handler, and thermostat. Fault codes appear on the Infinity Touch thermostat under the System menu → Current Status → Alerts. The outdoor unit’s control board also has a status LED that blinks a simplified fault code for technicians working without thermostat access.
Carrier categorizes faults as alerts (informational, system still running) and faults (system locked out). The thermostat shows both types.
| Code | Fault Description |
|---|---|
| 14 | Low ambient temperature lockout, outdoor temp below equipment operating limit |
| 24 | High pressure switch trip |
| 25 | Low pressure switch trip |
| 26 | Discharge temperature exceeded cutout |
| 27 | Loss of charge (low pressure alert before full lockout) |
| 33 | Outdoor fan motor fault |
| 34 | Outdoor unit communication fault (no signal on Infinity bus) |
| 41 | Outdoor ambient temperature sensor failure |
| 42 | Outdoor coil temperature sensor failure |
| 43 | Discharge temperature sensor failure |
| 44 | Suction temperature sensor failure |
| 45 | Liquid line temperature sensor failure |
| 53 | Inverter module communication fault, no signal from inverter to main board |
| 54 | Inverter module fault, internal error (overcurrent, overtemp, undervoltage) |
| 55 | Compressor protection, inverter detected locked rotor or phase imbalance |
| 57 | Compressor contactor fault |
| 63 | Reversing valve fault |
| 65 | Defrost cycle fault |
| 168 | Air handler communication fault, outdoor unit lost contact with indoor unit |
| 178 | EEV (electronic expansion valve) drive fault |
| 179 | EEV position fault, valve not responding to drive commands |
| 185 | Supply voltage fault, L1-L2 outside acceptable range |
| 200 | Control board internal fault |
These three codes come up most often on the 24VNA6 because they relate to the communicating system and EEV, which are unique to variable-speed Infinity units.
Code 168 (Air handler communication fault): The outdoor unit’s control board has lost communication with the air handler’s communicating control board. This shuts down the entire system because the outdoor unit cannot receive indoor coil temperature data needed to run the inverter safely. Root causes: disconnected or damaged communication wire, failed air handler control board, or power loss to the air handler.
Code 178 (EEV drive fault): The electronic expansion valve’s stepper motor driver circuit on the outdoor control board has failed or is not getting a response from the EEV motor. The EEV is the heart of the 24VNA6’s efficiency, it continuously adjusts refrigerant flow to match the inverter’s variable output. Without EEV control, the system cannot run safely.
Code 179 (EEV position fault): Distinguishable from 178, this means the driver circuit is functioning but the valve itself isn’t responding as commanded. The EEV may be mechanically stuck, or the stepper motor connector may have a broken pin. This code also appears when the EEV loses its reference position after a power outage, requiring a valve home cycle (usually clears automatically on next startup).
Inverter faults (codes 53–55): The Greenspeed inverter module (Carrier uses a module manufactured by Hitachi or equivalent) converts 240V single-phase power to variable-frequency output for the scroll compressor. Code 53 means the main control board can’t see the inverter module at all, check the communication harness between boards. Code 54 is an internal inverter fault; a Carrier service tool can pull sub-codes. Code 55 means the inverter tried to start the compressor but the compressor didn’t respond, winding failure or rotor lock.
| Part | Why You Need It | Approx. Cost |
|---|---|---|
| Carrier Outdoor Sensor HH79NZ074 | Ambient and coil sensor replacement for codes 41, 42; 10k NTC thermistor | $20–$45 |
| Carrier 24VNA6 Outdoor Control Board | Required for EEV driver failure (code 178) or control board fault (code 200) | $250–$550 |
| Carrier Infinity Touch Thermostat | Required for full Infinity fault code display on the 24VNA6 | $200–$400 |
| High Pressure Switch Carrier Heat Pump | Replace if code 24 persists with normal refrigerant pressures | $25–$60 |
| Reversing Valve Solenoid Coil 24V | Required when code 63 trips with confirmed 24V at solenoid terminals | $20–$45 |
| Refrigerant Manifold Gauge Set R-410A | Essential for diagnosing pressure faults 24, 25, 27 accurately | $45–$120 |
Need replacement parts? Search for parts and tools on Amazon.
The 24VNA6 Greenspeed is not a system for DIY refrigerant work or inverter diagnosis:
Sensor replacements, pressure switch swaps, and communication wiring troubleshooting are within reach for a qualified DIYer or general HVAC service technician.
Q: The Carrier Infinity thermostat shows code 168 and 42 at the same time. Where do I start? A: Start with code 168 (air handler communication). The outdoor coil sensor (code 42) may actually be fine, a communication loss between outdoor and indoor units prevents the thermostat from reading the outdoor sensors correctly, which can generate phantom sensor faults. Restore communication first, then see if code 42 clears on its own.
Q: My 24VNA6 only runs at full speed and won’t modulate down. No fault codes. What’s happening? A: The Greenspeed needs a fully functioning Infinity communicating system to modulate. Check that the thermostat and air handler are both on the bus and showing “Connected” in the thermostat’s system status. If the outdoor unit can’t communicate with the indoor unit, it defaults to maximum capacity as a fail-safe. Also check whether the iQ Drive sub-code shows any inverter limitation in service diagnostics.
Q: How often does the 24VNA6 defrost in winter, and when should I be concerned? A: Normal defrost cycles occur every 30–90 minutes during heating operation in cold, humid weather (30–45°F outdoor). Each cycle lasts 5–10 minutes. If the unit is going into defrost more than once per hour or defrost cycles are lasting 15+ minutes, that’s abnormal. Common causes: low refrigerant charge (low suction pressure = coil ices faster), failed defrost sensor not reading coil temperature correctly, or outdoor fan running at too low a speed in variable mode.
Q: Code 185 (voltage fault) appeared after a summer storm. The unit won’t run. What do I check first? A: Check your main electrical panel for a tripped breaker or a breaker that appears on but has internally tripped (flip it fully off, then back on). If the panel looks fine, check the outdoor disconnect for a blown fuse or tripped disconnect. Then measure L1-L2 voltage at the outdoor unit’s contactor with a multimeter. Carrier specifies 208–240VAC; anything below 187V or above 253V will trigger code 185. If voltage is consistently outside range, that’s a utility or panel issue for an electrician.
Carrier uses different diagnostic systems across furnaces, heat pumps, chillers, mini-splits, VRF equipment, rooftop units, and communicating controls. Confirm the full model number and whether the fault came from the indoor board, outdoor board, thermostat, or equipment controller before matching it to a repair path.
Start with power, wiring, airflow or water-flow, sensor, condensate, and safety-circuit checks before ordering control boards. If the same code returns after one reset and the basic cause is not obvious, test the named circuit instead of repeatedly cycling the equipment.
Parts note: For 24VNA6 Greenspeed faults, prioritize model-matched outdoor sensors, pressure switches, communication parts, inverter boards, and fan components from the part table above.