Burnham boiler flame rod assembly
Price when cleaning no longer restores stable flame current.
Burnham Err 4 and Err 6 guide for flame-current faults, flame rods, grounding, igniters, gas valves, control boards, and unsafe flame signals.
Burnham Err 4 and Err 6 guide for flame-current faults, flame rods, grounding, igniters, gas valves, control boards, and unsafe flame signals.
Parts to price first
Price when cleaning no longer restores stable flame current.
Relevant when Err 4 persists with a clean flame rod and good ground.
Technician-level replacement when Err 6 points to a stuck valve.
Price only after flame rod, wiring, grounding, and gas valve checks pass.
A Burnham boiler displaying Err 4 has detected a weak or failing flame signal. The control board is not receiving enough microamps through the flame rod to confirm the burner is lit. Err 6 is the opposite problem. The control board detects a flame signal when the gas valve is closed and the burner should be off.
Both codes point to problems in the flame sensing circuit but require different diagnostic approaches. Err 4 is more common. Err 6 is rarer and often involves a stuck gas valve or electronic noise.
| Code | Description | Likely Cause | Severity |
|---|---|---|---|
| Err 4 | Flame current low | Dirty flame rod, weak igniter, bad wiring, no ground path | Medium |
| Err 6 | Flame sensed out of sequence | Stuck gas valve, control board failure, electrical noise | High |
| b08 | Pressure switch open with inducer on | Blocked vent, failed switch, restricted condensate | Medium |
| b09 | Pressure switch closed with inducer off | Stuck switch, shorted wiring | Medium |
| b26 | Safety limit circuit open | High limit tripped, rollout switch, blocked airflow | Medium |
This is the most common Burnham error on Series 2 and Alpine boilers. The flame sensor rod carries a microamp DC current through the flame to ground. If the rod is dirty or the ground path is poor, current drops below the 1-2 microamp threshold.
Start here:
Err 6 is a safety code. The control board will lock out and require a manual reset. This means the board detected a flame signal at a time when the gas valve was commanded closed.
Diagnosis:
| Part | Estimated Cost | When to Replace |
|---|---|---|
| Flame rod assembly | $30-60 | Every 2-3 seasons or when cleaning no longer restores signal |
| Igniter | $40-90 | When Err 4 persists with clean rod and good ground |
| Gas valve | $150-400 | When Err 6 is confirmed with stuck valve |
| Control board (UCB-2 or equivalent) | $200-500 | When all other causes are ruled out |
| Tool | Use |
|---|---|
| Fine abrasive pad | Cleaning flame rod |
| Microamp meter | Testing flame current (target: 2-8 microamps DC) |
| Multimeter | Testing gas valve solenoid continuity and ground path |
| Screwdriver set | Removing burner access panels |
Call a licensed boiler technician if any of these apply:
Safety note: Err 6 can indicate a gas valve that is leaking through the seat. If you suspect a stuck-open gas valve, shut off the gas supply immediately and call a professional.