Allen-Bradley PowerFlex F002 Fault - Auxiliary Input Trip

⚡ Quick Answer

PowerFlex F002 means auxiliary input trip. Check the wired interlock, overload relay, safety relay, loose terminals, and input parameter.

⚡ AT A GLANCEScroll down for full repair guide
What it meansPowerFlex F002 means auxiliary input trip. Check the wired interlock, overload relay, safety relay, loose terminals, and input parameter.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededVFD-rated motor cable
Repair intent

Need this fixed instead of diagnosed?

PowerFlex F002 means auxiliary input trip. Check the wired interlock, overload relay, safety relay, loose terminals, and input parameter.

Likely parts to price

Price the common parts before you book service.

VFD-rated motor cable

First part to price when insulation damage or output-cable leakage is found.

Output line reactor

Useful on long motor leads after true insulation faults are ruled out.

Motor terminal kit

Relevant when moisture, tracking, or damaged terminals cause leakage faults.

Allen-Bradley PowerFlex Fault F002 — What It Means

Allen-Bradley PowerFlex fault F002 means Auxiliary Input — a digital input configured as an external fault or auxiliary interlock has been activated (opened or closed, depending on configuration). The PowerFlex 4, 40, 70, and 700 series all use F002 for this purpose. The drive is not detecting a fault in its own electronics; it’s responding to an external signal on a digital input terminal. Until the signal condition clears and the fault is reset, the drive won’t run. This is a wiring and integration problem, not a drive component failure.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Identify which input is configured for Aux Fault — Navigate to the digital input parameters (P036–P038 on PowerFlex 40, or equivalent on your model). Find which terminal is configured as “Aux Fault.”
  2. Check the wiring at that terminal — At the drive’s I/O terminal block, verify the auxiliary input wire is present and firmly seated. A missing wire means the input is floating (open), which typically triggers the fault.
  3. Trace the external circuit — Follow the wire from the drive terminal back to whatever device it connects to (safety relay, overload, interlock). Is the contact closed? Use a multimeter to measure continuity across the contact.
  4. Check the external device — If it’s a motor overload relay, has it tripped? Reset it. If it’s a safety relay, check whether the safety system has detected an actual safety condition.
  5. Reset the system — After the auxiliary circuit is restored (contact closed, wiring intact), press the drive’s Stop/Reset button or cycle the enable input. F002 should clear.

Parts Often Needed

PartNotes
Terminal block wire (18–22 AWG)Replace if the auxiliary input wire is damaged
Motor overload relayIf the external device that tripped is the overload; reset or replace
Safety relay (Pilz, Allen-Bradley GuardMaster)If the safety circuit is the interlock source and it has failed

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

If F002 appears and no external device is wired to the auxiliary input terminal, a controls technician should review the drive parameters and program the unused input as “Not Used” to prevent false trips.